v2.00
Ariterm Oy
21.5.2013
12
AUTOMATIC
If the burner is set to
Automatic
mode, the burner will activate the
Effect
-
mode, when the flame detection system detects a flame. Burner effect is
adjusted on a scale of 20-100%. If the flame detection does not detect a
flame, the system activates the controlled ignition phase (see section 11.
Ignition)
SHUTDOWN
This function stops the storage system operation and the funnel is no longer
filled. The system continues to operate as long as the burner screw and funnel
contain fuel. The operation stops, when the
Alarm!
Flame
alarm is displayed.
The function can be used, for example, during preparations for boiler and
burner maintenance.
In buffer tank use, the shutdown function is activated automatically, when the
lower temperature of the buffer tank exceeds its setting. The burner will
remain in standby mode. The start-up command is given when the buffer tank
upper temperature falls below the set temperature.
STOP
This button stops all devices of the system, except for the cooling pump and
the smoke gas fan which must be stopped with their dedicated buttons.
SWEEPING
This button controls the convection sweeping motor, overriding their
scheduled functions.
ASH SCREW
This button controls the ash screws, overriding their scheduled functions.