Effect
Figure 10. EFFECT -settings
Setting
Factory
setting
Setting
frequency
Function
Temperature setting
80°C
0-100°C
Set boiler water temperature. The
burner maintains the set
temperature.
Measured temperature
True value -
10…150°C True boiler water temperature.
Temperature
hysteresis
5°C
0-50°C
If the boiler water temperature
increases above the set boiler water
temperature by the amount of the
hysteresis, the burner activates the
maintenance mode. When the
boiler water temperature decreases
by 0.5 x hysteresis, the burner
switches back to power mode (E.g.
at 82.5°C)
Effect
True value 0-100%
True burner power
Manual effect setting
21%
20-100%
Burner power in manual operation
mode. The burner will run at a
constant power, until the boiler
water temperature increases over
the set temperature by the amount
of hysteresis.
Temperature sensor
scaling min
-10
-
150...150°C
Boiler water temperature scaling.
NOTE! Requires Maintenance level
password.
Temperature sensor
scaling max
150
-
150…150°C
Boiler water temperature scaling.
NOTE! Requires Maintenance level
password.