9
commissioning
gas setting
parameter
4 kW
30 kW
38 kW
G0
G31
G0
G31
G0
G31
lower Wobbe index
(15°C, 1013 mbar) (MJ/m3)
45,67 70,69 45,67 70,69 45,67 70,69
minimum fan speed(%)
33
05
05
01
01
01
01
maximum central heating fan speed (%)
34
85
85
80
80
70
70
maximum D.H.W fan speed (%)
3
98
98
89
89
89
89
gas valve restrictor(ø)
NO
3,80
NO
4,50
NO
5,50
gas flow max/min
(15°C, 1013 mbar)
(nat - m3/h) (GPL - kg/h)
max D.H.W
,65
1,94
3,17
,33
4,0
,95
max C.H.
,33
1,71
,96
,17
3,8
,41
min
0,58
0,43
0,69
0,50
0,79
0,58
Heating ignition delay adjustment
This parameter – menu /sub menu 3/parameter 5 - can be used
to manually (0) or automatically (1) set the delay time before the
subsequent reignition of the burner after it has switched off on
reaching the desired temperature in central heating mode.
By selecting manual, it is possible to set the delay in minutes using
the successive parameter (menu /sub menu 3/parameter 6), to a
time between 0 and 7 minutes.
Automatic selection means that the boiler will establish the delay
time based on the set-point temperature.