The blocking signal can also be tested in the commissioning phase by a software switch signal when
the relay's testing mode "Enable stage forcing" is activated (
General
→
Device).
The variables the user can set are binary signals from the system. The blocking signal needs to reach
the device minimum of 5 ms before the set operating delay has passed in order for the blocking to
activate in time.
Events and registers
The capacitor bank current unbalance protection function (abbreviated "UCP" in event block names)
generates events and registers from the status changes in ALARM START, ALARM, START, TRIP,
BLOCKED and HARMONIC BLOCK. The user can select which event messages are stored in the main
event buffer: ON, OFF, or both. The function offers one (1) independent stage.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.2.3 - 65. Event messages.
Event block name
Event names
UCP1
Alarm Start ON
UCP1
Alarm Start OFF
UCP1
Alarm ON
UCP1
Alarm OFF
UCP1
Start ON
UCP1
Start OFF
UCP1
Trip ON
UCP1
Trip OFF
UCP1
Block ON
UCP1
Block OFF
UCP1
Harmonic block ON
UCP1
Harmonic block OFF
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
Table. 5.3.2.3 - 66. Register content.
Date and
time
Event
Pre-
trigger
current
Fault
current
Prefault
current
Meas/AL set
Meas TR/set
Trip time
remaining Used SG
dd.mm.yyyy
hh:mm:ss.mss
Event
name
Start/
Trip -20
ms
current
Start/
Trip
current
Start
-200ms
current
The ratio
between the
measurement & the
alarm setting
The ratio of the
measurement &
the trip setting
0
ms...1800s
Setting
group 1...8
active
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
78
© Arcteq Relays Ltd
IM00035