Table. 5.3.20 - 187. General settings of the function.
Name
Range
Default
Description
Prev> LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
0: On
Set mode of RPW block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
Pick-up
The
P
set
rev.setting parameter controls the pick-up of the Pr function. This defines the maximum
allowed measured three-phase active power before action from the function. The function constantly
calculates the ratio between the
P
set
rev. and the measured magnitude (P
m
). The reset ratio of 97 % is
built into the function and is always relative to the
P
set
rev. value.
Table. 5.3.20 - 188. Pick-up settings.
Name
Description
Range
Step
Default
P
set
rev.
Pick-up setting
0.0…100 000kW
0.01kW
100kW
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.20 - 189. Information displayed by the function.
Name
Range
Step
Description
Prev> LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of RPW block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
Prev> condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays the status of the protection function.
Expected
operating time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs.
Time remaining
to trip
-1800.000...1800.000s 0.005s
When the function has detected a fault and counts down time
towards a trip, this displays how much time is left before tripping
occurs.
P meas/P set
at the moment
1250.00P
m
/P
set
0.01P
m
/P
set
The ratio between the measured power and the pick-up value.
Function blocking
The block signal is checked in the beginning of each program cycle. The blocking signal is received
from the blocking matrix in the function's dedicated input. If the blocking signal is not activated when
the pick-up element activates, a START signal is generated and the function proceeds to the time
characteristics calculation.