Figure. 5.3.2.2 - 37. Simplified function block diagram of the Cnu> function.
Measured input
The function block uses analog current measurement values from the residual current inputs I01 and
I02 as well as the three phase current measurement inputs. In the configuration of the function can be
selected which of the measurement inputs are used for the unbalance current measurement.
Signal
Description
Time base
IL1 CMPLX
The complex vector of IL1 (A) current measurements
5ms
IL2 CMPLX
The complex vector of IL2 (B) current measurements
5ms
IL3 CMPLX
The complex vector of IL3 (C) current measurements
5ms
I01 CMPLX
The complex vector of I01 current measurements
5ms
I02 CMPLX
The complex vector of I02 current measurements
5ms
The selection of the used neutral unbalance current measurement channel is made with a setting
parameter.
General settings
The following general settings define the general behaviour of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.3.2.2 - 54. General settings of the function.
Name
Range
Default
Description
CNU> (50UB)
LN mode
1: On
2: Blocked
3: Test
4: Test/
Blocked5:
Off
1: On
Set mode of CNU block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.