Pick-up
Figure. 5.3.2.3 - 38. Measurement connection of the Iuc> function.
The protection function uses a formula which takes the highest measured value of the phase's
current, then subtracts from this value the lowest measured value of the phase's current, and finally
divides the result with the mean of all phases. This value is then compared to the
Iset Alarm and
the
Iset Trip parameters. The function constantly calculates the ratio between the I
set
and the
calculated magnitude (
I
unb
). The reset ratio of 97 % is built into the function and is always relative to
the
I
set
value.
Table. 5.3.2.3 - 62. Pick-up settings.
Name
Range
Step
Default
Description
Iset Alarm
0.10…50.00×I
n
0.01×I
n
1.20×I
n
Defines the pick-up setting for the alarm.
Iset Trip
0.10…50.00×I
n
0.01×I
n
1.20×I
n
Defines the pick-up setting for the trip.
Definite time delay alarm
0.000…1 800.00s
0.005s
0.04s
Defines the definite time delay for the ALARM signal.
Definite time delay trip
0.000…1 800.00s
0.005s
0.04s
Defines the definite time delay for the TRIP signal.
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
76
© Arcteq Relays Ltd
IM00035