Table. 5.3.18 - 174. Measurement inputs of the P> function.
Signal
Description
Time base
3PH Active power (P)
Total three-phase active power
5ms
General settings
The following general settings define the general behavior of the function. These settings are static i.e.
it is not possible to change them by editing the setting group.
Table. 5.3.18 - 175. General settings of the function.
Name
Range
Default
Description
P> LN
mode
1: On
2: Blocked
3: Test
4: Test/
Blocked
5: Off
0: On
Set mode of OPW block.
This parameter is visible only when
Allow setting of individual LN mode is enabled in
General menu.
Pick-up
The
P
set
>setting parameter controls the pick-up of the P> function. This defines the maximum allowed
measured three-phase active power before action from the function. The function constantly calculates
the ratio between the
P
set
>and the measured magnitude (P
m
). The reset ratio of 97 % is built into the
function and is always relative to the
P
set
>value.
Table. 5.3.18 - 176. Pick-up settings.
Name
Description
Range
Step
Default
P
set
>
Pick-up setting
0.0…100 000kW
0.01kW
100kW
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Read-only parameters
The relay's
Info page displays useful, real-time information on the state of the protection function. It is
accessed either through the relay's HMI display, or through the setting tool software when it is
connected to the relay and its Live Edit mode is active.
Table. 5.3.18 - 177. Information displayed by the function.
Name
Range
Step
Description
P> LN
behaviour
1: On
2: Blocked
3: Test
4: Test/Blocked
5: Off
-
Displays the mode of OPW block.
This parameter is visible only when
Allow setting of individual LN
mode is enabled in General menu.
P> condition
0: Normal
1: Start
2: Trip
3: Blocked
-
Displays the status of the protection function.
Expected
operating
time
0.000...1800.000s
0.005s
Displays the expected operating time when a fault occurs.
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
200
© Arcteq Relays Ltd
IM00035