The inputs for the function are the following:
• setting parameters
• digital input signals
• measured and pre-processed current magnitudes.
The function's outputs are CLPU ACT and BLOCKED signals which can be used for direct I/O
controlling and user logic programming. The function generates general time-stamped ON/OFF events
to the common event buffer from each of the two (2) output signals. The time stamp resolution is 1 ms.
The function also provides a resettable cumulative counter for the CLPU ACT and BLOCKED events.
The following figure presents a simplified function block diagram of the cold load pick-up function.
Figure. 5.4.3 - 140. Simplified function block diagram of the cold load pick-up function.
Measured input
The function block uses analog current measurement values. A -20 ms averaged value of the selected
magnitude is used for pre-fault data registering.
Table. 5.4.3 - 235. Measurement inputs of the cold load pick-up function.
Signal
Description
Time base
IL1RMS
RMS measurement of phase L1 (A) current
5ms
IL2RMS
RMS measurement of phase L2 (B) current
5ms
IL3RMS
RMS measurement of phase L3 (C) current
5ms
The pre-fault condition is presented with a 20 ms averaged history value from -20 ms from CLPU
ACT event.