Figure. 5.4.3 - 145. Example of timers and pick-up parameters (no inrush current detected in the starting).
In the example above, the cold load pick-up function activates after the measured current has stayed
below the
I
low
setting for a
T
set
amount of time. The current stays between the
I
low
setting and the
I
high
setting, so the cold load pick-up signal is active for
T
min
time. As no inrush current is detected during
that time, the signal is released.