Name
Description
Range
Step
Default
Multi-criteria
detection
Activation of detecting healthy or unhealthy feeder by analyzing
symmetrical components of currents and voltages. Visible when
earthing type is set to I0
Cos
& I0
Sin
broad range mode.
1: Not used
2: Used
-
1: Not
used
Unearthed/
Compensated
border angle
Dividing the angle between unearthed and compensated
tripping (see description later in this document). Visible when
earthing type is set to I0
Cos
& I0
Sin
broad range mode.
-45.0…90°
0.1°
45°
Angle
Tripping area size (earthed network)
±45.0…135.0°
0.1°
±88°
Angle offset
Protection area direction (earthed network)
0.0…360.0°
0.1°
0.0°
Angle blinder
I0 angle blinder (Petersen coil earthed)
-90.0…0.0°
0.1°
-90°
The pick-up activation of the function is not directly equal to the START signal generation of the
function. The START signal is allowed if the blocking condition is not active.
Unearthed network
Figure. 5.3.6 - 47. Angle tracking of I0dir> function (unearthed network model) (32N)
A
AQ
Q-C255
-C255
Instruction manual
Version: 2.06
102
© Arcteq Relays Ltd
IM00035