● 0X111
Indicates the internal system error report of module 1~module 8. Figure 4.4
Figure 4.4
The address of FA in Figure 4.4 represents the system error report of each module. Examples are as
follows:
Module 1 and module 3 have a system error, the signal will become a LO signal, and it will be converted
to binary (1111 1010) at this time, and the binary signal will be converted to hexadecimal to get FA.
The address of F7 in Figure 4.4 represents the temperature error report of each module. Examples are
as follows:
When the module 4 has a temperature error, the signal will become a LO signal, at this time it will be
converted to binary (1111 0111), and then the binary signal is converted to hexadecimal to get F7
The address of FE in Figure 4.4 represents the output under voltage error report of each module.
Examples are as follows:
When the module 1 has an under-voltage error, the signal will become a LO signal, at this time it will be
converted to binary (1111 1110), and then the binary signal will be converted to hexadecimal to get FE
Module 8 Module 3
Module 1
Module 4
Module 1