HI Power Supply User Manual
Technical Sales / Customer Service:
+1-818-338-
7788 • Email:
31328 Via Colinas Suite 102 • Westlake Village, CA 91362 USA •
19 / 31
V+: DC module positive output.
V-: DC module negative output
3.3.2 Output Blocking Diode and Antiparallel Diode Recommendation
The HI-power modules can be used in a redundant parallel system by connecting the outputs together
via OR-ing diodes. For good regulation the remote sense connections must be made after the OR-ing
diode at the same point on the busbar or load. The remote sense leads should be the same length for
each power supply and a twisted pair should be used for best noise immunity. The current share lines
between the power supplies should be connected as shown in Figure 3.5.
Figure 3.5 Blocking diode for use when connecting modules in parallel