DeltaSol
®
BS/4
Stores cool down at night
Collector circuit pump
runs during the night?
no
yes
Check controller:
Manual operation active?
Tube collector function
active? Store cooling
or antifreeze function
active?
Collector temperature is
at night higher than the
outdoor temperature
no
yes
Check the check valve in
the flow and the return
pipe with regard to the
functional efficiency.
Sufficient store insulation?
yes
no
Increase insulation.
Insulation close enough
to the store?
yes
no
Replace insulation or in-
crease it.
Are the store connec-
tions insulated?
yes
no
Insulate the connections.
Warm water outflow
upwards?
no
yes
Change connection and
let the water flow hori-
zontally or through a si-
phon (downwards); less
store losses now ?
Does the warm water
circulation run for a very
long time?
no
yes
Use the circulation pump
with timer and switch-off
thermostat (energy ef-
ficient circulation).
The solar circuit pump does not work, although the col-
lector is considerably warmer than the store.
Is the control lamp (LED)
illuminated?
yes
no
Does the pump start up
in manual operation?
yes
There is no current; check
fuses / replace them and
check power supply.
The adjusted temperature
difference for starting the
pump is to high; choose a
value which makes more
sense.
no
Is the pump current ena-
bled by the controller?
yes
Is the pump stuck?
Turn the pump shaft us-
ing a screwdriver; now
passable?
Pump is defective - re-
place it
Are the controller fuses
o.k. ?
Controller might be defec-
tive - replace it or contact
the distributor.
no
yes
no
no
yes
Replace fuses.
Circulation pump and
blocking valve should be
switched off for one night;
less store losses?
yes
no
Check whether the pumps
of the afterheating circuit
run at night; check wheth-
er the non-return valve is
defective; problem solved ?
no
no
yes
o.k.
Control the non-return
valve in warm water cir-
culation - o.k.
yes
no
Further pumps which are
connected to the solar
store must also be checked.
The thermosiphoning in
the circulation line is too
strong; insert a stronger
valve in the non-return
valve or an electrical
2-port valve behind the
circulation pump; the
2-port valve is open when
the pump is activated, oth-
erwise it is closed; connect
pump and 2-port valve
electrically in parallel; ac-
tivate the circulation again
Clean or replace it
a
a
b
b
yes
o.k.