DeltaSol
®
BS/4
The thermostat function works independently from the
solar operation and can be used for using surplus energy
or for afterheating.
s
!(/
<
!(&
thermostat function for afterheating
s
!(/
>
!(&
thermostat function for using surplus energy
The symbol
will be shown on the display if the second
relay output is activated.
Thermostat function
Afterheating
!(/
Thermostat switch-on tem p.
Adjustment range:
0.0 ... 95.0 °C
[30.0 ... 200.0 °F]
in steps o
f 0.5 K [1.0 °Ra]
Factory setting:
40.0 °C [110.0°F]
!(&
Thermostat switch-off tem p.
Adjustment range:
0.0 ... 95.0 °C
[30.0 ... 200.0 °F]
in steps o
f 0.5 K [1.0 °Ra]
Factory setting:
45.0 °C [120.0 °F]
T/T/T/
Thermostat switch-on time
Adjustment range:
00:00 ... 23:45
Factory setting: 00:00
T&T&T&
Thermostat switch-off time
Adjustment range:
00:00 ... 23:45
Factory setting: 00:00
In order to block the thermostat function for a certain
period, there are three time frames t1 ... t3. If the function
should be active between 6:00 and 9:00, set
t1 O
to 6:00
and
T&
to 9:00.
If all time frames are set to 00:00 o’clock, the thermostat
function is continuously activated (factory setting).
Use of surplus energy
Reference sensor for the thermostat function is S3!
System-specific functions
The following functions are exclusively available in system
layout 2. The corresponding channels will not be available in
any other system layout.