Apricus DeltaSol BS/4 Manual Download Page 23

23 

|

© 12128_Apricus_DeltaSol_BS4_V2.monen.ind

d

DeltaSol

®

 BS/4

CMN

:

Collector minimum temp. 
Adjustment range: 
10 ... 90 °C [50 ... 190 °F]
in steps o

f 0.5 K [1 °Ra]

 

Factory setting: 
10 °C [50 °F]

Collector minimum limitation option

/#.

 

Collector minimum limitation 
Adjustment range: OFF / ON 
Factory setting: OFF

If  the  collector  minimum  limitation  option  is  activated, 
the  pump  (R1)  is  only  switched  on  if  the  adjustable 
collector minimum temperature is exceeded. The minimum 
temperature prevents the pump from being switched on too 
often at low collector temperatures. A fixed hysteresis of 
5 °K [10 °Ra] is set for this function
If the collector minimum limitation is active,   (flashing) is 
shown on the display.

Antifreeze option

/#&

 

Antifreeze function 
Adjustment range: OFF / ON 
Factory setting: OFF

The antifreeze function activates the loading circuit between 
the collector and the store when the temperature falls below 
the adjusted antifreeze temperature. This will protect the 
fluid against freezing or coagulating. If the adjusted antifreeze 
temperature is exceeded by 1 K [2 °Ra], the loading circuit 
will be deactivated.
When the antifreeze function is activated, 

 is shown on 

the  display.  If  the  antifreeze  function  is  active, 

 

and 

 

(flashing) are shown on the display.

.OTE

Since this function uses the limited heat quantity 
of the store, the antifreeze function should be 
used in regions with few days of temperatures 
around the freezing point.
The antifreeze function will be suppressed if the 
store temperature falls below 5 °C [40 °F] in 
order to protect the store from frost damage.

#&2

Antifreeze temperature 
Adjustment range: 
-40.0 ... +10.0 °C
[-40.0 ... +50.0 °F]
in steps o

f 0.5 K [1 °Ra]

 

Factory setting: 
4.0 °C [40.0 °F]

Store cooling function

When the store cooling function is activated, the controller 
aims to cool down the store during the night in order to 
prepare it for solar loading on the following day.
If the adjusted maximum store temperature 

S MX

 is 

exceeded and the collector temperature falls below the 
store temperature, the system will be reactivated in order 
to cool down the store. Cooling will continue until the store 
temperature has fallen below the adjusted maximum store 
temperature 

S MX

 again. A fixed hysteresis of 2 K [4 °Ra] 

is set for this function.
Reference threshold temperature differences for the store 
cooling function are 

DT O

 and 

$4&

.

If no DHW consumption is expected for a longer period of 
time, the additional holiday cooling option 

/(/,

can be 

activated in order to extend the store cooling function. The 
adjustable temperature 

4(/,

then replaces the maximum 

store temperature 

S MX

 as a switch-off temperature for the 

store cooling function.
When the holiday cooling function is activated

,

 

 and   

(flashing) are shown on the display. 
While the holiday cooling function is active, 

,

 

 and   

(flashing) are shown on the display.

/34#

 

Store cooling option 

 

Adjustment range: OFF / ON 
Factory setting: OFF

4(/,

Holiday cooling temperature 
Adjustment range: 
20 ... 80 °C [70 ... 175 °F]
in steps of 1 K [1 °Ra] 
Factory setting: 
40 °C [110 °F]

/(/,

Holiday cooling option 
Adjustment range: OFF / ON 
Factory setting: OFF

.OTE

If 

OSTC

 or 

/#&

 is active, the collector minimum 

function  will  be  overridden.  In  that  case,  the 
collector temperature may fall below 

CMN

.

Summary of Contents for DeltaSol BS/4

Page 1: ...n 11201745 11201745 DeltaSol BS 4 version 2 Mounting Connection Operation Application examples Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Delta...

Page 2: ...y possibly life threatening injury can occur ATTENTION means that damage to the appliance can occur CE Declaration of conformity The product complies with the relevant direc tives and is therefore lab...

Page 3: ...l data OUSING plastic PC ABS and PMMA 0ROTECTION TYPE IP 20 EN 60529 MBIENT TEMP 0 40 C 32 104 F 3IZE 172 110 47 mm 6 8 4 3 1 9 OUNTING wall mounting mounting into patch panels is possible ISPLAY Syst...

Page 4: ...with lower fastening screw and tighten Complete wiring connections in accordance with termi nal allocations see chap 1 2 Electrical connection Place the cover back onto the housing Fasten the cover by...

Page 5: ...f and the corresponding screws The controller is equipped with 2 semiconductor relays to which loads such as pumps valves etc can be connected s Relay 1 18 conductor R1 17 neutral conductor N 13 groun...

Page 6: ...18 COL x Temperature collector S1 18 TST x Temperature store S2 18 S3 x Temperature sensor 3 S3 18 TSTT x Temperatur store at the top S3 18 S4 x Temperature sensor 4 S4 18 TR x Temperature return sens...

Page 7: ...ure difference 20 0 K 40 0 Ra 22 DTCF x Cooling switch off temperature difference 15 0 K 30 0 Ra 22 OSTC x Option store cooling OFF 23 OHOL x Option holiday cooling OFF 23 THOL x Holiday cooling tempe...

Page 8: ...ess 18 COL x Temperature collector S1 18 TSTB x Temperature store 1 base S2 18 TSTT x Temperature store 1 at the top S3 18 TDIS s Thermal disinfection temperature S3 18 S4 x Temperature sensor 4 S4 18...

Page 9: ...ending time 19 00 24 TCRU x OTC runtime 30 s 24 TCIN x OTC standstill interval 30 min 24 OHQM x Option heat quantity measurement OFF 24 FMAX x Maximum flow 6 0 l 24 MEDT x Antifreeze type 1 24 MED x...

Page 10: ...0 200 0 F in steps of 0 5 K 1 0 Ra Factory setting 45 0 C 120 0 F T T T Thermostat switch on time Adjustment range 00 00 23 45 Factory setting 00 00 T T T Thermostat switch off time Adjustment range 0...

Page 11: ...ng the afterheating Reference sensor for the thermal disinfection is S3 To activate the function select On in the OTD channel For thermal disinfection the temperature in the upper DHW store zone has t...

Page 12: ...l Page COL x Temperature collector S1 18 TST x Temperature store S2 18 S3 x Temperature sensor 3 S3 18 TSTT x Temperatur store at the top S3 18 S4 x Temperature sensor 4 S4 18 TR x Temperature return...

Page 13: ...OFF 21 EM x Emergency temperature collector 130 C 270 F 21 CMX s Maximum collector temperature 110 C 230 F 22 OCN x Option minimum limitation OFF 23 CMN x Minimum collector temperature 10 C 50 F 23 OC...

Page 14: ...ring normal operation only the display channels are shown Scroll through the display channels by pressing buttons 1 and 2 CCESSING THE ADJUSTMENT CHANNELS Scroll down in the display menu and press but...

Page 15: ...or fault sensor symbol is flashing quickly LASHING CODES LED flashing codes System screen flashing codes Pump Store with heat exchanger Afterheating with burner symbol Temperature sensor Collector wit...

Page 16: ...ons 1 and 2 Save the adjustment by pressing button 3 again The symbol stops flashing Press button 1 or 2 to switch to the next or previous channel 1 2 3 OK The three pushbuttons of the BS 4 controller...

Page 17: ...ypical settings to suit the selected system layout The settings made in the commissioning menu can be changed later on in the corresponding adjustment channels Additional functions and options can of...

Page 18: ...Arr 1 and 3 only s S4 temperature sensor 4 3 3 Sensor temperatures Display range 40 260 C 40 500 F Indication of return temperature If heat quantity measurement is active the temperature at sensor 4 i...

Page 19: ...quantity can be set back to 0 As soon as one of the display channels of the heat quantity is selected the symbol is permanently shown on the display Press button 3 for about 2 seconds in order to acc...

Page 20: ...ump speed increases by one step 10 If the difference increases by the adjustable rise value the pump speed increases by 10 respectively until the maximum pump speed of 100 is reached The response of t...

Page 21: ...re limitation Emergency shutdown of the collector Store emergency shutdown option If the adjusted collector emergency shutdown temperature EM is exceeded the controller switches off the solar pump R1...

Page 22: ...hot days If the store temperature is higher than the maximum store temperature S MX and the switch on temperature difference DTCO is reached the solar system remains activated Solar loading is contin...

Page 23: ...w 5 C 40 F in order to protect the store from frost damage 2 Antifreeze temperature Adjustment range 40 0 10 0 C 40 0 50 0 F in steps of 0 5 K 1 Ra Factory setting 4 0 C 40 0 F Store cooling function...

Page 24: ...m speed nMN If the collector sensor is defective or the collector is blocked this function is suppressed or switched off EAT QUANTITY MEASUREMENT If OHQM is activated the heat quantity gained can be c...

Page 25: ...l initiate the filling of the system when solar loading begins If the drainback option is activated the pump will operate at 100 speed for the adjusted filling time T in order to fill the system with...

Page 26: ...selection Selection dE En Fr Factory setting En HE pump control Adjustment range ON OFF Factory setting OFF 5NIT In this adjustment channel the display unit for temperatures and temperature difference...

Page 27: ...8 888 8 Cable broken Check cable Short circuit Check cable Disconnected Pt1000 temperature sen sors can be checked with an ohmmeter In the following table the resistance values with the corresponding...

Page 28: ...exchanger blocked yes no Clean it Heat exchanger too small yes Replace with correctly sized one no Plausibility control of the option tube col lector special function Change Ton and Toff correspondin...

Page 29: ...yes no Does the pump start up in manual operation yes There is no current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a...

Page 30: ...s and from a larger distance An additional power supply is not required Large Display GA3 The Large Display GA3 is designed for simple connection to controllers via theVBus It is used for visualizing...

Page 31: ...VBus of the controller and issues an optical signal via a red LED if a failure has occurred The AM1 also has a potential free relayoutput which can e g be connected to a building management system BM...

Page 32: ...s espe cially applies for copies translations microfilms and the storage into electronic systems Editor Apricus Australia Pty Ltd Important notice The texts and drawings in this manual are correct to...

Reviews: