When a starting time for thermal disinfection with starting 
delay is adjusted in 

SDIS

, the thermal disinfection will be 

delayed until that time, even after the 

CDIS

 has counted 

down to 00:00. If 

CDIS

 ends, for example, at 12:00 o‘clock, 

and 

SDIS

 has been set to 18:30, relay 2 will be operated 

with a delay of 6.5 hours at 18:30 instead of 12:00.
During the waiting time, 

SDIS

 is displayed with the adjusted 

starting time (flashing).
If, during the waiting time, the temperature at S3 exceeds 

TDIS

 for the adjusted heating period 

DDIS

, thermal 

disinfection is considered complete and a new monitoring 
period begins.
If the starting time is adjusted to 00:00 (factory setting), the 
delay function is inactive.

Upon delivery, 

OTD

 is deactivated. The adjustment values 

PDIS

TDIS

DDIS 

and

 SDIS

 are displayed after the 

option has been activated. After the thermal disinfection 
function has been completed, the values will be “hidden” 
and the monitoring period will be displayed. 

SDIS 

 

Starting time 
Adjustment range:  
00:00 ... 24:00 (o‘clock) 
Factory setting: 00:00

Thermal disinfection with starting delay

/PTION4HERMALDISINFECTIONOFTHEUPPER$(7
ZONE/4$ 

TDIS 

 

Disinfection temperature 
Adjustment range: 
0 ... 95 °C [30 ... 200 °F]
in steps of 1 K [2 °Ra]
Factory setting: 
60 °C [140 °F]

DDIS

  

Heating period 
Adjustment range: 
00:00 ... 23:59 (hh:mm) 
Factory setting: 01:00 

PDIS

Monitoring period 
Adjustment range:  
0 ... 30:0 ... 24 h (dd:hh) 
Factory setting: 01:00

This function is used for protecting the upper store zone 
against Legionella by activating the afterheating.

Reference sensor for the thermal disinfection is S3!

 

Î

To activate the function, select “On” in the 

OTD

 

channel.

For thermal disinfection, the temperature in the upper 
DHW store zone has to be monitored. This protection is 
ensured when, during the monitoring period (

PDIS

), the 

disinfection temperature (

TDIS

) is continuously exceeded 

for the entire heating period (

DDIS

). S3 is used as the 

reference sensor and displayed as 

TSTT

.

If 

OTD

 is activated, 

PDIS

 will start as soon as the tem-

perature at S3 falls below 

TDIS

. In the display channel 

CDIS,

 the remaining time of 

PDIS

 is counted backwards. 

If, during the monitoring period, the temperature at S3 
exceeds 

TDIS

 continuously for the duration of 

DDIS

thermal disinfection is considered complete and a new 
monitoring period begins.
If 

CDIS

 counts down to 00:00, relay 2 will be operated 

in order to use the afterheating for thermal disinfection. 

CDIS

 will then be replaced with a display channel 

DDIS

 

showing the adjusted heating period. 

DDIS

 will start coun-

ting down the heating period as soon as 

TDIS

 is exceeded 

at S3. As long as 

DDIS

 is active, the temperature at S3 will 

be displayed as 

TDIS

 instead of 

TSTT

.

If, during 

DDIS

, the temperature at S3 exceeds 

TDIS

 by 

more than 5 K [10 °Ra], relay 2 is switched off until the 
temperature falls below 

TDIS

 + 2 K [4 °Ra].

If, during 

DDIS

, the temperature at S3 falls below 

TDIS

the heating period will restart. 

DDIS

 can only be com-

pleted when 

TDIS

 is exceeded without interruption.

Due to the flexible control logic, the exact time of thermal 
disinfection is not predictable. In order to set a fixed time 
for the disinfection to be run, the starting delay 

SDIS

 must 

be employed:

OTD

Thermal disinfection function 
Adjustment range: ON / OFF 
Factory setting: OFF

Summary of Contents for DeltaSol BS/4

Page 1: ...n 11201745 11201745 DeltaSol BS 4 version 2 Mounting Connection Operation Application examples Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Delta...

Page 2: ...y possibly life threatening injury can occur ATTENTION means that damage to the appliance can occur CE Declaration of conformity The product complies with the relevant direc tives and is therefore lab...

Page 3: ...l data OUSING plastic PC ABS and PMMA 0ROTECTION TYPE IP 20 EN 60529 MBIENT TEMP 0 40 C 32 104 F 3IZE 172 110 47 mm 6 8 4 3 1 9 OUNTING wall mounting mounting into patch panels is possible ISPLAY Syst...

Page 4: ...with lower fastening screw and tighten Complete wiring connections in accordance with termi nal allocations see chap 1 2 Electrical connection Place the cover back onto the housing Fasten the cover by...

Page 5: ...f and the corresponding screws The controller is equipped with 2 semiconductor relays to which loads such as pumps valves etc can be connected s Relay 1 18 conductor R1 17 neutral conductor N 13 groun...

Page 6: ...18 COL x Temperature collector S1 18 TST x Temperature store S2 18 S3 x Temperature sensor 3 S3 18 TSTT x Temperatur store at the top S3 18 S4 x Temperature sensor 4 S4 18 TR x Temperature return sens...

Page 7: ...ure difference 20 0 K 40 0 Ra 22 DTCF x Cooling switch off temperature difference 15 0 K 30 0 Ra 22 OSTC x Option store cooling OFF 23 OHOL x Option holiday cooling OFF 23 THOL x Holiday cooling tempe...

Page 8: ...ess 18 COL x Temperature collector S1 18 TSTB x Temperature store 1 base S2 18 TSTT x Temperature store 1 at the top S3 18 TDIS s Thermal disinfection temperature S3 18 S4 x Temperature sensor 4 S4 18...

Page 9: ...ending time 19 00 24 TCRU x OTC runtime 30 s 24 TCIN x OTC standstill interval 30 min 24 OHQM x Option heat quantity measurement OFF 24 FMAX x Maximum flow 6 0 l 24 MEDT x Antifreeze type 1 24 MED x...

Page 10: ...0 200 0 F in steps of 0 5 K 1 0 Ra Factory setting 45 0 C 120 0 F T T T Thermostat switch on time Adjustment range 00 00 23 45 Factory setting 00 00 T T T Thermostat switch off time Adjustment range 0...

Page 11: ...ng the afterheating Reference sensor for the thermal disinfection is S3 To activate the function select On in the OTD channel For thermal disinfection the temperature in the upper DHW store zone has t...

Page 12: ...l Page COL x Temperature collector S1 18 TST x Temperature store S2 18 S3 x Temperature sensor 3 S3 18 TSTT x Temperatur store at the top S3 18 S4 x Temperature sensor 4 S4 18 TR x Temperature return...

Page 13: ...OFF 21 EM x Emergency temperature collector 130 C 270 F 21 CMX s Maximum collector temperature 110 C 230 F 22 OCN x Option minimum limitation OFF 23 CMN x Minimum collector temperature 10 C 50 F 23 OC...

Page 14: ...ring normal operation only the display channels are shown Scroll through the display channels by pressing buttons 1 and 2 CCESSING THE ADJUSTMENT CHANNELS Scroll down in the display menu and press but...

Page 15: ...or fault sensor symbol is flashing quickly LASHING CODES LED flashing codes System screen flashing codes Pump Store with heat exchanger Afterheating with burner symbol Temperature sensor Collector wit...

Page 16: ...ons 1 and 2 Save the adjustment by pressing button 3 again The symbol stops flashing Press button 1 or 2 to switch to the next or previous channel 1 2 3 OK The three pushbuttons of the BS 4 controller...

Page 17: ...ypical settings to suit the selected system layout The settings made in the commissioning menu can be changed later on in the corresponding adjustment channels Additional functions and options can of...

Page 18: ...Arr 1 and 3 only s S4 temperature sensor 4 3 3 Sensor temperatures Display range 40 260 C 40 500 F Indication of return temperature If heat quantity measurement is active the temperature at sensor 4 i...

Page 19: ...quantity can be set back to 0 As soon as one of the display channels of the heat quantity is selected the symbol is permanently shown on the display Press button 3 for about 2 seconds in order to acc...

Page 20: ...ump speed increases by one step 10 If the difference increases by the adjustable rise value the pump speed increases by 10 respectively until the maximum pump speed of 100 is reached The response of t...

Page 21: ...re limitation Emergency shutdown of the collector Store emergency shutdown option If the adjusted collector emergency shutdown temperature EM is exceeded the controller switches off the solar pump R1...

Page 22: ...hot days If the store temperature is higher than the maximum store temperature S MX and the switch on temperature difference DTCO is reached the solar system remains activated Solar loading is contin...

Page 23: ...w 5 C 40 F in order to protect the store from frost damage 2 Antifreeze temperature Adjustment range 40 0 10 0 C 40 0 50 0 F in steps of 0 5 K 1 Ra Factory setting 4 0 C 40 0 F Store cooling function...

Page 24: ...m speed nMN If the collector sensor is defective or the collector is blocked this function is suppressed or switched off EAT QUANTITY MEASUREMENT If OHQM is activated the heat quantity gained can be c...

Page 25: ...l initiate the filling of the system when solar loading begins If the drainback option is activated the pump will operate at 100 speed for the adjusted filling time T in order to fill the system with...

Page 26: ...selection Selection dE En Fr Factory setting En HE pump control Adjustment range ON OFF Factory setting OFF 5NIT In this adjustment channel the display unit for temperatures and temperature difference...

Page 27: ...8 888 8 Cable broken Check cable Short circuit Check cable Disconnected Pt1000 temperature sen sors can be checked with an ohmmeter In the following table the resistance values with the corresponding...

Page 28: ...exchanger blocked yes no Clean it Heat exchanger too small yes Replace with correctly sized one no Plausibility control of the option tube col lector special function Change Ton and Toff correspondin...

Page 29: ...yes no Does the pump start up in manual operation yes There is no current check fuses replace them and check power supply The adjusted temperature difference for starting the pump is to high choose a...

Page 30: ...s and from a larger distance An additional power supply is not required Large Display GA3 The Large Display GA3 is designed for simple connection to controllers via theVBus It is used for visualizing...

Page 31: ...VBus of the controller and issues an optical signal via a red LED if a failure has occurred The AM1 also has a potential free relayoutput which can e g be connected to a building management system BM...

Page 32: ...s espe cially applies for copies translations microfilms and the storage into electronic systems Editor Apricus Australia Pty Ltd Important notice The texts and drawings in this manual are correct to...

Reviews: