Installation and Service Manual – Metered Carbon Filter
Page 16
Copyright © 2012 Applied Membranes, Inc. All Rights Reserved.
Filter System Setup
Note: The Filter Valve will come pre-programmed with the default settings indicated in table 6. The below reference is for
reprogramming in the case of a valve reset, or if a different setting is desired.
STEP 1F
Press NEXT and
▼
buttons simultaneously for 3 seconds. If screen in step 2F does
not appear in 5 seconds the lock on the valve is activated. To unlock press
▼
, NEXT,
▲
, and SET CLOCK in sequence, then press NEXT and
▼
simultaneously for 3
seconds.
STEP 2F
Choose “FILTERING” using
▼
or
▲
buttons.
Press NEXT to go to Step 3F. Press REGEN to exit OEM Filter System Setup.
STEP 3F
Enter “oFF” (to turn off regenerant refill) using
▼
or
▲
buttons.
Press NEXT to go to Step 4F. Press REGEN to return to previous step.
STEP 4F
Backwash mode – Select using
▼
or
▲
buttons.
(See table 4 for backwash cycle times)
“NORMAL” for SINGLE NORMAL backwash
Default/Recommended
“NORMAL 2” for DOUBLE NORMAL length backwash
“LONGER” for SINGLE LONGER length backwash
“LONGER 2” for DOUBLE LONGER length backwash
Press NEXT to go to Step 5F. Press REGEN to return to previous step.
STEP 5F
Set Gallons Capacity using
▼
or
▲
buttons.
“oFF” = regeneration based on day override (time clock operation);
or:
Number of gallons (20 to 50,100) for demand initiated regeneration.
Press NEXT to go to Step 6F. Press REGEN to return to previous step.
STEP 6F –Refill Option: Skipped, because “OFF” is selected in in step 3F
Press NEXT to go to Step 7F. Press REGEN to return to previous step.
STEP 7F
Set Regeneration Time Option using
▼
or
▲
buttons:
“NORMAL” means regeneration will occur at the next preset time when the gallons
capacity reaches zero.
“on 0” means regeneration will occur immediately when the gallons capacity
reaches zero
“ on 0” means regeneration will occur after 10 minutes of no water
usage after the gallon capacity reaches zero.
Press NEXT to exit Filter System Setup. Press REGEN to return to previous step.