MND
Rev. A, 6/15
18
•
COMM
(Communications)
bAUd R
(Baud Rate): 2400, 9600, 19200, 38400
PARITY
: even, odd, none
STOPbT
(Stop Bit): 1, 2
NOTE: all APG Modbus based sensors communicate using 9600 baud, no parity and 1
stop bit.
C TYPE
(Communications Type):
MASTER
: sets the MND to operate as the master device.
SNIFER
(Sniffer): sets the MND to passively monitor communications between
a master device and one or more sensors. The master device must be actively polling
the sensor(s) in order for the MND to update the reading(s).
LRSNIF
(LOE/RST Sniffer): functions the same as Sniffer mode with addition of
monitoring the readings from an LOE series or RST-5000 series Ethernet based sensor
(acting as the master device).
SETUP
: sets the MND to act operate as a “slave” device in order to be
programmed using the APG Modbus software.
NOTE: the Sensor Address parameter (see below) is used to set the MND’s own
sensor address when operating in Setup mode.
SENAdR
(Sensor Address): sets the address number of the sensor to be displayed
when only one sensor is being monitored. The Sensor Address is also used to set the
MND’s own address when operating in Setup mode.
NOTE: in order to monitor readings from multiple sensors, the assigned sensor
address numbers must begin at 1 and increment sequentially. For example, if 5
sensors are to be monitored, the sensor addresses must be set to 1 thru 5.
NOTE: when displaying the readings from multiple sensors, the Sensor Address setting
determines which sensor is controlling the output(s) of the MND.
www.
.com
1.800.561.8187