MPX Series Magnetostrictive

Input Registers (0x04):

Register 

Type  

Returned Data

30300   

U16 

Raw Top Float Reading (in mm, unsigned)

30301   

U16 

Raw Bottom Float Reading (in mm, unsigned)

30302   

S16 

Temperature Reading (in 

0

C, signed)

30303-30304 

U32 

Calculated Top Float Reading (in selected Units) 

30305-30306 

U32 

Calculated Bottom Float Reading (in selected Units) 

Holding Registers (0x03):

Register  

Type 

Description

     Value Range

40400   

U16 

Device Address 

 

 

1 to 255

40401    

U16 

Units 

 

 

 

1 to 3 

 

40402    

U16 

Application Type    

 

0-10

40403    

U16 

Volume Units  

 

 

0 to 6 

40404   

U16 

Decimal Place 

 

 

0 to 3

40405   

U16 

Max Distance 

 

 

0 to 10364 mm

40406    

U16 

Full Distance  

 

 

0 to 10364 mm

40407    

U16 

Empty Distance    

 

0 to 10364 mm 

40408   

U16 

Sensitivity 

 

 

0 to 100

40409 

 U16 

Pulses 

   0 

to 

20

40410 

 U16 

Blanking 

   0 

to 

10364 

mm

40411 

  reserved 

  

40412 

 U16 

Averaging   0 

to 

100

40413   

U16 

Filter Window 

 

 

0 to 10364 mm

40414   

U16 

Out of Range Samples 

 

0 to 255

40415   

U16 

Sample Rate 

 

 

50 to 1000 msec.

40416   

U16 

Multiplier 

 

 

1 to 1999

40417   

S16 

Offset 

 

 

 

+/- 10364 mm

40418-40420 

 reserved 

   

40421   

S16 

RTD Offset (0C) 

 

 

-100 to 100

40422     

U16 

Float Window 

 

 

0 to 1000 mm 

40423     

U32 

Top Float Offset 

 

 

+/- 10364 mm

40424     

U32 

Bottom Float Offset  

 

+/- 10364 mm

40425     

U32 

Gain Offset 

 

 

0 to 255

40426-40435 

 

 

 reserved 

   

40436-40437    U32 

Parameter 1 Data   

 

0 to 100000 mm 

40438-40439    U32 

Parameter 2 Data   

 

0 to 100000 mm  

40440-40441    U32 

Parameter 3 Data    

 

0 to 100000 mm

40442-40443    U32 

Parameter 4 Data   

 

0 to 100000 mm 

40444-40445    U32 

Parameter 5 Data   

 

0 to 100000 mm

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for MND

Page 1: ...Operator s Manual AUTOMATION P R O D U C T S GROUP INC Automation Products Group Inc MND Modbus Network Display DOC 9003708 Rev A 6 15 www com information itm com 1 800 561 8187...

Page 2: ...hift 11 Multiplier 11 Bar Graph 11 Overload 12 Battery Indicator 12 Outputs 13 17 Analog Settings 13 Solid State Relay Settings 13 16 Switchable Power Source 17 Communications Settings 18 20 Sensor La...

Page 3: ...le handling improper application or use of the goods or from any other cause relating thereto and APG s liability hereunder in any case is expressly limited to the repair or replacement at APG s optio...

Page 4: ...Brown 24 VDC 24 VDC Relay Power 2 White RS 485 A RS 485 A RS 485 A 3 Blue DC Ground 4 20 mA Out DC Ground 4 Black RS 485 B RS 485 B RS 485 B No connection for MND s with internal batteries 2 1 4 3 5 C...

Page 5: ...B RS 485 B 5 Grey N C N C N C Analog Out No connection for MND s with internal batteries 6 pin Tajimi No Output 4 20 mA Switchable Power 0 3 VDC A 24 VDC 24 VDC Relay Power 24 VDC B DC Ground 4 20 mA...

Page 6: ...Grey Com 1 Com 1 2 6 Pink Com 2 NO NC 2 7 Blue DC Ground DC Ground 8 Red NO NC 2 Analog Out 1 2 3 4 5 6 7 8 8 C Cable 22 AWG 2 NO NC Relays 0 3 VDC 2 Relays 24 VDC Red Red DC Ground Black Black RS 485...

Page 7: ...1 second to power on or off the MND Function within Setup Menu press to cycle downward through menu options or decrease mode setting values Enter Button Function in Operating Mode cycles between the...

Page 8: ...ons are accessible including those that may not be applicable to all MND configurations 001 Locks access to all setup menus The Increase Button will scroll through sensor readings when the MND is conf...

Page 9: ...4 SEN 8 SEN 9 SEN 7 LOERST EXIT EXIT EXIT SEN 10 MOdE bRTNES AVERGE SAM RT ENTR UNITS MAXMIN TEMP C TEMP F CU FT MCU FT CU M GALLON LITERS CU IN PCTFUL CUSTOM bARREL EXIT EXIT AL CAL AH CAL T1TYPE T2...

Page 10: ...y display PCTFUL percent full for any reading being displayed in Percent Full mode see page 20 for more information ENTR Enter Button Function Selects the function of the ENTER button when in standard...

Page 11: ...f the least significant digit s up to 3 places so that masked digit s will always display 0 and will not increment SHIFT Digit Shift allows the user to shift the reading to the right by dividing the r...

Page 12: ...n 5 digit limit of the display bAT EN Battery Enabled allows the user to select either No Battery Internal Battery or RST Battery options The Internal Battery option is used to monitor the voltage of...

Page 13: ...ation adjusts the high end of the analog output i e either 20mA or 3V Increasing decreasing the value will cause an increase decrease at the high end of the analog output T1TYPE T2TYPE Trip 1 2 Type d...

Page 14: ...int the output will deactivate and remain in that state until the reading is less than the Trip Reading FAR The output will activate whenever the reading is greater than the Trip Reading NOTE for Norm...

Page 15: ...s than the Trip Reading Trip Window H FAR Hysteresis Far The output will activate when the reading increases beyond the Trip Reading Trip Window and will remain active until the reading falls below th...

Page 16: ...al in seconds NOTE when using the Timed Interval in conjunction with the Auto Off feature the MND will wake power on at each Interval and will remain powered on for the duration of the relay On Time r...

Page 17: ...determines how long power is supplied to the sensor APG recom mends an On Time of 8 10 seconds to allow the sensor enough time to power up and get a reading The Auto Off setting determines how long t...

Page 18: ...s the master device SETUP sets the MND to act operate as a slave device in order to be programmed using the APG Modbus software NOTE the Sensor Address parameter see below is used to set the MND s own...

Page 19: ...for the register to be displayed 3 holding resister 4 input register Sensor readings are stored in input registers while sensor parameter values are stored in holding registers REGTYP Register Type se...

Page 20: ...s No select Yes to write the new register value and complete the procedure or No to cancel the write and return to the Communications menu Write function example changing the Empty Distance value regi...

Page 21: ...cent Full feature select PCTFUL in the main menu Select the sensor number you want to display as a percentage of full and enter the value associated with 100 0 empty is assumed to be 0 Setting the val...

Page 22: ...ved configuration back to the MND see page 25 Use the following steps to establish communications and program the MND via the APG Modbus software Step 1 Use the buttons on the MND to enter the Communi...

Page 23: ...ssigned to the RS 485 to RS 232 converter being used Step 7 Select MND Step 6 Ensure Sensor matches the Sensor Address setting in the MND Step 8 Once all the changes have been made click Save Config t...

Page 24: ...he MND Step 11 To change multiple parameters individually click on the values you wish to change enter the desired values then click the Send All button at the bottom of the window to write all the va...

Page 25: ...eviously saved settings configuration to the MND click on File then se lect Load Mode Values Choose a file you wish to upload then click Open This will load the parameter values into the software Clic...

Page 26: ...1 6 C Type Master Number of Sensors 6 Sensor Address 3 Register Number 303 Function 4 Register Type U32 unsigned 32 bit MND in Sniffer mode displaying readings from a single sensor address 3 C Type S...

Page 27: ...Shift 0 Multiplier 1 000 Bar Graph 0 0 Bar Graph 100 10000 Over Load 99999 max display value Battery Gauge Enable No Battery Battery Full 13 5 V Battery Low 11 0 V Analog Low Reading 0 Analog High Re...

Page 28: ...Output Input Voltage Requirements 9 Vdc min no load to 28 Vdc max Signal Variance 0 16 mA at set points Output Input 2 wire loop powered Resolution 14 bit Protection reversed polarity 0 3 VDC Output I...

Page 29: ...407 U16 Empty Distance 0 to 10364 mm 40408 U16 Sensitivity 0 to 100 40409 U16 Pulses 0 to 20 40410 U16 Blanking 0 to 10364 mm 40411 U16 Gain Control 0 to 4 40412 U16 Averaging 0 to 100 40413 U16 Filte...

Page 30: ...m 40407 U16 Empty Distance 0 to 10364 mm 40408 U16 Sensitivity 0 to 100 40409 U16 Pulses 0 to 20 40410 U16 Blanking 0 to 10364 mm 40411 reserved 40412 U16 Averaging 0 to 100 40413 U16 Filter Window 0...

Page 31: ...AUTOMATION To order additional copies of this manual ask for APG document number 9003708 Rev A 6 15 P R O D U C T S GROUP INC Automation Products Group Inc www com information itm com 1 800 561 8187...

Reviews: