“ON” TIME
(in seconds)
Relay “ON” (closed)
Relay “OFF”(open)
INTERVAL TIME
(in minutes)
LOERST
(LOE/RST):
forces the output to follow the state of the corresponding output of an LOE or RST
sensor acting as the master device. For example, whenever output T1 of the LOE/RST
activates/deactivates, then output T1 of the MND will activate/deactivate as well.
TIME R
*(Timed Interval):
sets the output to activate on a timed interval. The Interval-Time (
INTMIN
) sets the
time between activations (in minutes), and the On-Time (
ON SEC
) determines how
long the output remains active at each interval (in seconds).
NOTE: when using the Timed Interval in conjunction with the Auto-Off feature, the
MND will wake (power on) at each Interval and will remain powered on for the
duration of the relay On-Time regardless of the Auto-Off setting.
*Also refer to Switchable Power Source Option on next page.
H TEMP
* (Heater Temperature):
The LCD heater is controlled using Trip Relay 1. Set the heater “on” temperature using
the Trip 1 Reading (
T1READ
) parameter (in
0
C). The Trip 1 Window (
T1 WIN
)
parameter is used to set the “off” temperature, defined by the number of degrees above
the on temperature.
For Example: to activate the heater at -30
0
C and deactivate the heater above -10
0
C
T1TYPE
set to
H TEMP
T1READ
set to
-0030
T1 WIN
set to
00020