MND
Rev. A, 6/15
12
OVR-Ld
(Overload): allows the user to set an overload warning if the reading
increases beyond the specified value.
NOTE: when displaying the readings from multiple sensors, the Overload setting
will be applied to the readings of all the sensors and cannot be set for each sensor
individually. By default the Overload is set to 99999 so that the overload warning will
only be displayed when a sensor reading is greater than 5-digit limit of the display.
bAT EN
(Battery Enabled): allows the user to select either No Battery, Internal
Battery or RST Battery options. The Internal Battery option is used to monitor the
voltage of a battery powered MND. The RST Battery option is used to monitor the
supply voltage of an RST-5000 module acting as the master device.
NOTE: the Internal battery indicator is limited to battery voltages less than 15 Vdc.
bATFUL
(Battery Full Voltage): sets the voltage associated with a full battery
indication.
bATLOW
(Battery Low Voltage): sets the voltage associated with a low battery
indication.