AIR QUALITY
MOBILE
50P
Jan 2012
Automatikprodukter
d) remove the cell and leave it to dry in a warm place, keeping it raised from the ground by wooden strips
(ovens with a maximum temperature of 60°C are tolerated).
e) examine the state of the ionisation wires, stretching them slightly to check their mechanical strength. Use
a cotton flock and methylated spirits to remove any residual traces of dirt.
f) Ensure that the cell is thoroughly clean and dry before reinstalling it.
When maintaining the pre-filter, first remove the dust deposited in it using an ordinary vacuum cleaner. Then
proceed with washing as follows:
a) Immerse the pre-filter in the tray containing the detergent diluted in warm water and leave to soak for
about half an hour.
b) Remove the pre-filter from the tray and rinse thoroughly with water.
c) Leave to dry in a warm ventilated environment.
5 . 2
G E N E R A L I N S P E C T I O N O F T H E F I L T E R S
The state of the filters must be inspected every time they are washed so as to prevent air cleaner malfunction
and problems.
INSPECTION
FAULT
OPERATION
ionisation wires
breakage of a wire
change the ionisation wire
ionisation wires
rough surface with material
deposits
clean the wire with a cloth soaked
in alcohol or replace
ceramic insulators
dirty with material deposits
wash the cell again
ceramic insulators
breakage or presence of cracks
replace the insulators
high voltage terminal strip
burning caused by high voltage
replace the high voltage terminal
strip
The following inspections must be made on the filters:
-
check that the internal mesh of the pre-filter is compact and that no wires protrude from the containing
meshes.
-
check that the frame is not deformed or damaged.
If the pre-filter is badly damaged, replace it with a new one.
5 . 3
C L E A N I N G T H E M A C H I N E
To clean the outside, use a cloth sprayed with methylated spirits.
Use a brush with soft bristles to clean the air outlet fins.
To clean the inlet grill, use a vacuum cleaner with a dusting attachment.