AIR QUALITY
MOBILE
50P
Jan 2012
Automatikprodukter
3 . 1
V E N T I L A T I N G T H E P R E M I S E S
All rooms where people are present carrying out any activity must be fitted with appropriate apparatuses
which guarantee adequate reoxygenation of the environment.
This reoxygenation is fundamental for the well-being of people and must be realised bearing in mind that
every person needs at least 12.5m
3
of air every hour where there is a high-efficiency air purification system.
It is therefore necessary to provide the premises with an air introduction system in proportion to the average
number of people present in them.
To calculate the quantity of air in m
3
/h to introduce from the exterior, it is sufficient to multiply the average
number of persons present by a coefficient of 12.5.
3 . 2
F I L T E R U N I T
There are two different filters in the machine:
-metal pre-filter 50P
-electrostatic cell 50P
3 . 3
M E T A L P R E - F I L T E R
The metal pre-filter is for trapping the bigger particles present in the air and for distributing the flow uniformly.
Depending on the model it is fitted in, it can have different dimensions which are illustrated below.
DIMENSIONS
FILTER MODEL
A
B
C
50p
344
310
6
During operation, the metal pre-filter must always be inserted in its seat.
During maintenance, it must be handled with care to prevent deformation or damage