APPENDICES
89
SERVICE PROCEDURE
D24-V
Flue Baffle Removal, Inspection
Step 1.
Disconnect (unplug) water heater from electrical supply.
Step 2.
Disconnect venting from draft diverter and remove draft
diverter from top of water heater.
Step 3.
Disconnect flue damper from wire harness and remove
flue damper from top of water heater (see photo 27).
Step 4.
If required, turn “OFF” water supply & disconnect top plumbing
connection from top of water heater.
Step 5.
Remove screws holding jacket head to top of water heater
and remove jacket head from top of water heater. Note, it may
be necessary to use a screw driver to pry underneath
jacket head (see photo 28).
Step 6.
Remove insulation from top of water heater to expose
collector cover.
Step 7.
Remove screws from side (or top) of collector cover. Note, it may be
necessary to chisel away some foam to access screws (see photo 29).
Step 8.
Remove collector cover from water heater by using
pipe wrench as illustrated in photo 30.
Step 9.
Remove flue baffles from water heater. Note, it may be necessary
to use pliers to loosen and remove baffles from flue tubes (see photo 31).
Step 10.
Visually inspect flue baffles. Flue baffles may show signs
of oxidation; this is normal. If the oxidation has deteriorated
any portion of the flue baffle, replacement is recommended.
If any restrictors are missing, replacement is recommended.
Step 11.
Upon completion of inspection or subsequent replacement,
reinstall flue baffles into heater.
Step 12.
Reinstall collector cover and insulation over collector cover.
Step 13.
Reinstall jacket head, flue damper and draft diverter. Reconnect venting.
Step 14.
Reconnect plumbing connection to top of water heater
& turn on water supply if required.
Step 15.
Check for leaks and verify proper operation.
WARNING
Heater components may be HOT when performing the following steps in this procedure.
Take necessary precaution to prevent personal injury.
Page 35
28
27
29
30
Flue Baffle
31
Summary of Contents for 24/39
Page 11: ...11 INSTALLATION SECTION 3 Standard Range Hi FloRange Fig3a Fig3b ...
Page 19: ...19 INSTALLATION SECTION 3 Fig 6A Fig 7 ...
Page 23: ...23 INSTALLATION SECTION 3 WATER CONNECTIONS Fig 9 Fig 10 ...
Page 26: ...26 INSTALLATION SECTION 3 WATER CONNECTIONS Fig 13 Fig 14 ...
Page 29: ...29 INSTALLATION SECTION 3 WATER CONNECTIONS Fig 17 Fig 18 ...
Page 52: ...52 PARTS LIST AND ILLUSTRATIONS SECTION 9 Hi Flo Models 62 341 and 54 418 440 ...
Page 93: ...93 Notes ...
Page 94: ...94 Notes ...
Page 95: ...95 Notes ...