AMD5x Passive Infeed Unit and AMD5x Servo Drive - User Guide
ANCA MOTION
D-000129 Rev 09
40
Example Cooling Duct Design
4.3.6
A suitable cooling duct system can be created with folded sheet-metal as per
1
8
9
.5
84
Figure 4-5: Cooling Duct with typical dimensions
The duct must have no air leaks, and is mounted
onto the rear of the gear tray with PIU and Drives
.
Each PIU
and Drive has a rubber gasket surrounding the heatsink to provide a seal between the duct and cabinet
preventing air from the duct entering the cabinet. Refer to
to allow even air flow the duct must extend
past the last Drive, and provide 60 to 90mm of space between the fans and PIU heatsink.
Figure 4-6: AMD5x system fan clearance to first PIU heatsink
Refer to
for side views with duct showing fan and heat sinks
Figure 4-7: Duct exit view