A01-00159 Rev B
22
09: Programmable outlets enable/disable
Interface
Setting
Parameter 2:
Enable or disable
programmable outlets.
ENA:
Programmable outlets enable
DIS:
Programmable outlets disable (Default)
10: Programmable outlets setting
Interface
Setting
Parameter 2:
Set up backup time limits for
programmable outlets.
0-999:
setting the backup time limits in
minutes from 0-999 for programmable outlets
which connect to non-critical devices on
battery mode. (Default: 999)
11: Autonomy limitation setting
Interface
Setting
Parameter 2:
Set up backup time on battery
mode for general outlets.
0-999:
setting the backup time in minutes
from 0-999 for general outlets on battery
mode.
DIS:
Disable the autonomy limitation and the
backup time will depend on battery capacity.
(Default)
Note:
When setting as “0”, the backup time
will be only 10 seconds.
12: Battery total AH setting
Interface
Setting
Parameter 2:
Set up the battery total AH of
the UPS.
7-999:
setting the battery total capacity from
7-999 in AH. Please set the correct battery
total capacity if external battery bank is
connected.