A01-00159 Rev B
21
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2:
Enable or disable Bypass
function. You may choose the following two
options:
ENA:
Bypass enable
DIS:
Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high
voltage point and acceptable low voltage
point for Bypass mode by pressing the Down
key or Up key.
HLS:
Bypass high voltage point
For 100/110/115/120/127 VAC models:
120-140:
setting the high voltage point
in parameter 3 from 120Vac to 140Vac.
(Default: 132Vac)
LLS:
Bypass low voltage point
For 100/110/115/120/127 VAC models:
85-115:
setting the low voltage point in
parameter 3 from 85Vac to 115Vac. (Default:
85Vac)
08: Bypass frequency range setting
Interface
Setting
Parameter 2:
Set the acceptable high
frequency point and acceptable low
frequency point for Bypass mode by
pressing the Down key or Up key.
HLS:
Bypass high frequency point
For 50Hz output frequency models:
51-55Hz:
setting the frequency high loss
point from 51Hz to 55Hz (Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz:
setting the frequency high loss
point from 61Hz to 65Hz (Default: 63.0Hz)
LLS:
Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz:
setting the frequency low loss
point from 45Hz to 49Hz (Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz:
setting the frequency low loss
point from 55Hz to 59Hz (Default: 57.0Hz)