A01-00159 Rev B
20
03: Output frequency setting
Interface
Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery
mode:
BAT 50:
presents output frequency is 50Hz
BAT 60:
presents output frequency is 60Hz
If converter mode is enabled, you may
choose the following output frequency:
CF 50:
presents output frequency is 50Hz
CF 60:
presents output frequency is 60Hz
04: ECO enable/disable
Interface
Setting
Parameter 2:
Enable or disable ECO
function. You may choose the following two
options:
ENA:
ECO mode enable
DIS:
ECO mode disable (Default)
05: ECO voltage range setting
Interface
Setting
Parameter 2:
Set the acceptable high
voltage point and low voltage point for ECO
mode by pressing Down key or Up key.
HLS:
High loss voltage in ECO mode in
parameter 2.
For 100/110/115/120/127 VAC models, the
setting range in parameter 3 is from +3V to
+12V of the nominal voltage.
(Default: +6V)
LLS:
Low loss voltage in ECO mode in
parameter 2.
For 100/110/115/120/127 VAC models, the
setting voltage in parameter 3 is from -3V to
-12V of the nominal voltage.
(Default: -6V)