132
16I-9xB Module Specifications
INPUT CIRCUIT
Input circuits are suitable for alarm or control switch inputs and are optically isolated with a transient protection
network on each input circuit.
Filtering
: 50/60Hz Digital Filtering. Rejecting of inputs less than 16mS
duration.
Series Mode Rejection
: 10V rm 50Hz with 30 ohm source resistance.
Common Mode Rejection
: 100V rms 50Hz between initiating contact and earth.
Source Resistance
: 200K ohms minimum loop resistance contact open.
: 1K ohms maximum loop resistance contact closed.
Surge Test
: BS EN 60060-2; 1995.
50Hz Rejection
: Induced 500V @ 50Hz between input and ground.
Input Current (approx.)
: 2.6mA per input.
WETTING VOLTAGE
16I-90B :
24V system
(minimum 21V, maximum 27V smooth d.c.)
16I-92B :
50V system
(minimum 44V, maximum 63V smooth d.c)
16I-95B :
125V system (minimum 100V, maximum 150V smooth d.c)
SUPPLY
5V ± 0.25V @ 40mA approx.
COMPATIBITY TABLE
The DMS-3K module range is fully backwards compatible with previous versions of this product, namely:
MPAS90
(Highland Electronics Limited)
RTU3000
Rochester Instrument systems Limited
DMS3000
AMETEK Power Instruments Limited
The 16I modules are backward compatible per the following table
DMS-3K MODULE
COMPATIBLE MODULES
Module Ref
Part No*
Module Ref
Part No
Comment
16I-90B
1087-437
16I-90B
2702-430
Single Part Edge Connector
16I-90A
8025-146
24 VDC FCV, Internally Supplied
16I-91A
8025-188
24 VDC FCV, Externally Supplied
16I-90
-
24 VDC FCV, Internally Supplied
16I-91
-
24 VDC FCV, Externally Supplied
16I-92B
1087-435
16I-92B
2702-457
Single Part Edge Connector
16I-92A
8025-210
48 VDC FCV, Internally Supplied
16I-95B
1087-440
16I-95B
2702-458
Single Part Edge Connector
16I-95A
8025-240
125 VDC FCV, Externally Supplied
(*Assembly Part Numbers listed include Front Panel and Wiring Connectors)
Summary of Contents for DMS-3K
Page 2: ......
Page 10: ......
Page 12: ......
Page 15: ...Page 3...
Page 19: ...Page 7 Logic Box Diagram...
Page 30: ...18 Approvals...
Page 46: ...34...
Page 105: ...Page 93 of 206 Figure 3 28 Option Upgrade Page...
Page 108: ......
Page 118: ...106 Logic Box Diagram...
Page 119: ...Page 107 of 206 Logic Box Motherboard Outline...
Page 120: ...108 3U Logic Box Motherboard Schematic Front View...
Page 121: ...Page 109 of 206 6U Logic Box Motherboard Schematic Front View...
Page 136: ...124 I O Modules Typical Alarm Circuit Arrangement...
Page 154: ...142 I R Module...
Page 155: ...Page 143...
Page 156: ...144 8 RR Module...
Page 157: ...Page 145...
Page 158: ...146 16 RR Module...
Page 159: ...Page 147...
Page 182: ......
Page 188: ......
Page 194: ......