62
Control/Sequence Group:
This is used to assign the control input to any of 8 groups. The groups correspond to specific
alarm inputs as configured in the Alarm Inputs page. For example: If you wanted a test
pushbutton to only operate specific alarm inputs, you would designate that group number for
the test pushbutton and assign it to all inputs in the Alarm Inputs configuration page.
Control Group 1 is a global ‘system-wide’ group that controls all inputs regardless of which
control group is assigned.
For example: If Input channel #23 is configured for Control Group 4 (reference the Alarm Inputs
Configuration screen), any pushbutton assigned to Control Group 4 will control that input
channel #23. In addition, any pushbutton assigned to Control Group 1 will also control the same
input channel #23.
Inhibit Group:
Similar to above but with the Inhibit Switch inputs.
Channel:
This will display an abbreviation of the control switch and group number configured.
Operating Sequence Configuration:
Up to 12 operating sequences can be configured for each Logic Card Rack. The available
operating sequences are:
•
ISA-A
Automatic reset with lock-in of alarms
•
ISA-A-4
Automatic reset with no lock-in of alarms
•
ISA-A-4-5-6 Automatic reset, non-locking, no flash, no audible, NO PB
•
ISA-M
Manual Reset with lock-in of alarms
•
ISA-F1A-1 First Out Flash, Subsequent alarm steady, auto reset
•
ISA-F2A-1 First Out, Fast Flash, auto reset
•
ISA-F2M-1 First Out, no subsequent alarm flash, manual reset
•
ISA-F3A
First Out, triple flash, first out reset
•
ISA-F3M
First out, triple flash, first out manual reset
•
ISA-FFAM2 First Out, manual reset
•
ISA-R
Ringback, separate flash for return to normal
•
ISA-R-12
Automatic Momentary Ringback, dual flash, manual reset
Refer to Appendix H for a list of all operating Sequences and their operation.
Control Interlock:
This requires that the Silence, Acknowledge and Reset pushbuttons are pressed in this exact
order. Anything else will be ignored.
For example; if the Acknowledge pushbutton is pressed before the Silence, it will not have any
effect. (Note: If the Reset function is not required for the alarm sequence selected, it will be
ignored.)
Summary of Contents for DMS-3K
Page 2: ......
Page 10: ......
Page 12: ......
Page 15: ...Page 3...
Page 19: ...Page 7 Logic Box Diagram...
Page 30: ...18 Approvals...
Page 46: ...34...
Page 105: ...Page 93 of 206 Figure 3 28 Option Upgrade Page...
Page 108: ......
Page 118: ...106 Logic Box Diagram...
Page 119: ...Page 107 of 206 Logic Box Motherboard Outline...
Page 120: ...108 3U Logic Box Motherboard Schematic Front View...
Page 121: ...Page 109 of 206 6U Logic Box Motherboard Schematic Front View...
Page 136: ...124 I O Modules Typical Alarm Circuit Arrangement...
Page 154: ...142 I R Module...
Page 155: ...Page 143...
Page 156: ...144 8 RR Module...
Page 157: ...Page 145...
Page 158: ...146 16 RR Module...
Page 159: ...Page 147...
Page 182: ......
Page 188: ......
Page 194: ......