Alarm Outputs Configuration
Notes:
•
Input #1-8 are assigned to Lamp outputs #1-8
(8 I/O card in slot #1)
•
Input #9-16 are assigned to Lamp outputs #9-16
(8 I/O card in slot #2)
•
I/R Card installed in slot #10 corresponds to Outputs 129,130,131 as shown
•
Output 129 configured as a Horn with all inputs assigned to it. Auto-silence configured
for 10 seconds. (It will operate when any input 1-16 goes into alarm and will be
silenced by either the Acknowledge pushbutton or automatically in 10 seconds)
•
Output 130 configured as a ‘Group Relay - Alarm Output’, follows field contact,
assigned to inputs 1-8. (It will operate when any input 1-8 goes into alarm and stay
activated until all alarms return to normal)
•
Output 131 configured as a ‘Group Relay - Alarm Output’, follows field contact,
assigned to inputs 9-16. (It will operate when any input 9-16 goes into alarm and stay
activated until all alarms return to normal)
Summary of Contents for DMS-3K
Page 2: ......
Page 10: ......
Page 12: ......
Page 15: ...Page 3...
Page 19: ...Page 7 Logic Box Diagram...
Page 30: ...18 Approvals...
Page 46: ...34...
Page 105: ...Page 93 of 206 Figure 3 28 Option Upgrade Page...
Page 108: ......
Page 118: ...106 Logic Box Diagram...
Page 119: ...Page 107 of 206 Logic Box Motherboard Outline...
Page 120: ...108 3U Logic Box Motherboard Schematic Front View...
Page 121: ...Page 109 of 206 6U Logic Box Motherboard Schematic Front View...
Page 136: ...124 I O Modules Typical Alarm Circuit Arrangement...
Page 154: ...142 I R Module...
Page 155: ...Page 143...
Page 156: ...144 8 RR Module...
Page 157: ...Page 145...
Page 158: ...146 16 RR Module...
Page 159: ...Page 147...
Page 182: ......
Page 188: ......
Page 194: ......