Page
6
to
62
SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY.
Mounting the unit by screwing the three screws as shown below.
It’s recommended to use M4 or M5 screws.
Battery Connection
CAUTION:
For safety operation and regulation compliance, it’s requested to install a separate DC over-current
protector or disconnection device between battery and the inverter. It may not be necessary to have a
disconnection device in some applications, however, it’s still recommended to have over-current protection
installed. Please refer to typical amperage as required.
WARNING!
All wiring must be performed by a qualified personnel.
WARNING!
It's very important for system safety and efficient operation to
use appropriate cables for battery connection. To reduce risk of injury,
please use the proper recommended cable in the table below.
Recommended battery cable size:
Ring terminal:
Model
Typical
Amperage
Wire
Size
Cable mm
2
(each)
Ring Terminal
Torque
Value
Dimensions
D (mm)
L (mm)
SPCIII4000-24
165A
2*4AWG
25
8.4
33.2
5 Nm
SPCIII6000-48
124A
1*2AWG
35
8.4
39.2
2*4AWG
25
8.4
33.2