e Setu
LCD Setting
General Setting
After pressing and holding “
” button for 3 seconds, the unit will enter th
p Mode. Press “
” or “ ” button
to select setting programs. Press “
” button to confirm you selection or “
” button to exit.
Setting Programs:
Program
Description
Selectable option
00
Exit setting mode
Escape
01
Output source priority:
To configure load power
source priority
Utility first (default)
Utility will provide power to the
loads as first priority.
Solar and battery energy will
provide power to the loads only
when
utility
power
is
not
available.
Solar first
Solar energy provides power to
the loads as first priority.
If solar energy is not sufficient to
power all connected loads, Utility
energy will supply power to the
loads at the same time.
SBU priority
Solar energy provides power to
the loads as first priority.
If solar energy is not sufficient to
power all connected loads,
battery energy will supply power
to the loads at the same time.
Utility provides power to the
loads only when battery voltage
drops to either low-level warning
voltage or the setting point in
program 12.
02
Maximum
charging
current: To configure total
charging current for solar
and utility chargers.
(Max. charging current =
utility charging current +
solar charging current)
60A (default)
Setting range is from 10A to
120A. Increment of each click is
10A.