Program
Description
Selectable option
23
Overload bypass:
When enabled, the unit
will transfer to line mode if
overload occurs in battery
mode.
Bypass disable (default)
Bypass enable
25
Record Fault code
Record enable (default)
Record disable
26
Bulk charging voltage
(C.V voltage)
SPCIII4000-24 default
setting: 28.2V
SPCIII6000-48 default setting:
56.4V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 25.0V to 31.5V for SPCIII4000-24
model and 48.0V to 61.0V for SPCIII6000-48 model. Increment
of each click is 0.1V.
27
Floating charging voltage
SPCIII4000-24
default
setting: 27.0V
SPCIII6000-48 default setting:
54.0V
If self-defined is selected in program 5, this program can be set
up. Setting range is from 25.0V to 31.5V for SPCIII4000-24
model and 48.0V to 61.0V for SPCIII6000-48 model. Increment
of each click is 0.1V.