Installation and assembly
The following applies to all work to be done:
NOTE.
Always comply with the relevant local accident
prevention regulations, statutory regulations,
guidelines and directives.
NOTE.
Note the sound information for the respective
model.
“Technical data /
scope of supply” overview,
“Sound” section.
INSTALLATION LOCATION
CAUTION.
Install the unit inside buildings only.
The installation room must be frost-free and dry.
WARNING!
Please note and follow the respective
relevant local standards, guidelines, directives
and regulations, especially the minimum
room volume necessary depending on the
quantity of refrigerant in the relevant heat
pump system (EN 378-1).
Refrigerant
Limit value
R 134a
0.25 kg/m³
R 404A
0.48 kg/m³
R 407C
0.31 kg/m³
R 410A
0.44 kg/m³
“Technical data /
scope of supply” overview,
“General unit data” section.
Minimum room volume =
Refrigerant capacity [kg]
Limit value [kg/m³]
NOTE.
If several heat pumps of the same type are installed,
only one heat pump must be considered.
If several heat pumps of different types are installed,
the heat pump requiring the largest room or space
must be considered.
TRANSPORT TO THE INSTALLATION LOCATION
To prevent damage during transport, always transport the
unit still packed to its final installation location using a pallet
truck.
If it is not possible to transport the unit to the final installa-
tion location using a pallet truck, you can also transport the
heat pump on a handcart or with tube handles.
Lifting the unit with tube handles.
WARNING!
The unit is not fixed on the wooden pallet.
Risk of tipping/overturning during transport!
People could be injured and equipment
damaged.
– Take suitable precautions to prevent the
risk of overturning.
ATTENTION
Never use components and hydraulic connections
on the unit for transport purposes.
ATTENTION
Do not tilt the unit by more than 45° maximum (in
any direction).