4
Subject to change without notice.
83054800bUK – Translation into English of the original German operating manual ait-deutschland GmbH
Intended use
The unit is only to be used for its intended purpose. This
means:
•
for heating.
•
for water heating.
The unit may be operated only within its technical
parameters.
“Technical data /scope of supply” overview.
NOTE.
Notify the responsible power supply company of
the use of a heat pump or heat pump system.
Disclaimer
The manufacturer is not liable for damage or losses resulting
from any use of the unit which is not its intended use.
The manufacturer's liability also expires:
•
if work is carried out on the unit and its components
contrary to the instructions in this operating manual.
•
if work is improperly carried out on the unit and its
components.
•
if work is carried out on the unit which is not
described in this operating manual, and this work has
not been explicitly approved by the manufacturer in
writing.
•
if the unit or components in the unit have been
changed, modified or removed without the explicit
written consent of the manufacturer.
EC conformity
The unit bears the CE marking.
EC Declaration of Conformity.
Safety
The unit is safe to operate when used for its intended
purpose. The construction and design of the unit conform
to current state-of-the-art standards, all relevant DIN/VDE
regulations and all relevant safety regulations.
Every person who carries out work on the unit must have
read and understood the operating manual before starting
any work. This also applies if the person concerned has
already worked with such a unit or a similar unit or has
been trained by the manufacturer.
Every person who carries out work on the unit must
comply with the applicable accident prevention and safety
regulations. This applies in particular to the wearing of
personal protective clothing.
DANGER!
Risk of fatal electric shock!
All electrical connection work must be
carried out by qualified electricians only.
Before opening the unit, disconnect the
system from the power supply - wait for
90 seconds = residual voltage at inverter -
and prevent it from being switched back on
again!
WARNING!
Only qualified personnel (trained heating,
refrigeration engineers and electricians)
may carry out work on the unit and its
components.
WARNING!
Unit contains refrigerant!
Leaking refrigerant could result in personal
injury and environmental damage. Therefore:
– Switch off system.
– Notify the manufacturer’s authorised
customer service.
ATTENTION
For safety reasons:
Never disconnect the unit from the power supply,
unless the unit is being opened.
ATTENTION
Install the heat pump indoors only and operate it
only with outside air as the heat source. The air
ducts must discharge outdoors. They must not be
constricted or blocked.