23
Subject to change without notice.
83054800bUK – Translation into English of the original German operating manual ait-deutschland GmbH Subject to change without notice.
Subject to change without notice.
83054800bUK – Translation into English of the original German operating manual ait-deutschland GmbH
REMOVING THE MASKING PLATE
In order to dismantle the masking plate, the latching
lugs must be completely released
on one side
by
pressing
towards the middle of the masking plate
.
Then release the latching lugs on the opposite side.
Commissioning
DANGER!
The unit may only be started up if the air
ducts, weather and/or rain louvres have been
installed and the facing panels are closed.
Carry out a thorough installation check and work
through the general checklist…
Manufacturer’s homepage.
By checking the installation you prevent damage to
the heat pump system, which could be caused by work
carried out improperly.
Check that…
•
clockwise rotary field
of the load power supply
(compressor) is ensured.
•
The heat pump
installation and assembly
have
been carried out according to the requirements of
this operating manual.
•
the electrical installation work has been completed
properly.
•
The power supply for the heat pump must be
equipped with an all-pole automatic circuit-breaker
with at least 3 mm contact spacing to IEC 60947-2.
•
The heating circuit is flushed, filled and thoroughly
vented.
•
All valves and shut-off devices of the heating circuit
are open.
•
All pipe systems and components of the system are
leaktight.
Carefully fill out and sign the completion report for
heat pump systems...
Manufacturer's homepage.
Within Germany and Austria:
Send completion report for heat pump systems
and general checklist to the manufacturer’s factory
customer service department…
In other countries:
Send completion report for heat pump systems and
general checklist to the manufacturer’s local partner…
The heat pump system is commissioned by customer
service personnel authorised by the manufacturer.
There is a fee for starting up!
SAFETY TEMPERATURE LIMITER
A safety temperature limiter is built into the electric heating
element (depending on model). If the heat pump fails or
there is air in the system, check whether the reset button
of this safety temperature limiter has triggered. If necessary,
push it in again.