3-10
Programming and Parameters
Basic Program Group
(continued)
P038 [Speed Reference]
Related Parameter(s):
,
,
-
Sets the source of the speed reference to the drive.
The drive speed command can be obtained from a number of different sources. The source is
normally determined by
[Speed Reference]. However, when
to option 1, 2, 3, 4, 5, 8, 14, 15, 16, 17 and the digital input is active, or if
[PID Ref Sel] is not set
to option 0, the speed reference commanded by
[Speed Reference] will be overridden. Refer to
the flowchart on
for more information on speed reference control priority.
Options
0
“Drive Keypad”
Internal frequency command from the digital speed keys on
the integral keypad.
1
“InternalFreq”
Internal frequency command from
[Internal Freq]. Must
be set when using MOP function.
2
“Analog In 1” (Default)
External frequency command from an analog source as
determined by
[Analog In 1 Sel] and DIP Switch AI1 on
the control board. Default Dip Switch setting is 10V.
3
“Analog In 2”
External frequency command from an analog source as
determined by
[Analog In 2 Sel] and DIP Switch AI2 on
the control board. Default Dip Switch setting is 10V.
4
“Preset Freq”
External frequency command as defined by
[Preset Freq x] when
-
programmed as “Preset Frequencies” and the digital inputs
are active.
5
“Comm Port”
External frequency command from the communications port.
Refer to Appendix D and Appendix E for details. Parameter
[Comm Format] is used to select a communications
protocol.
P039 [Accel Time 1]
Related Parameter(s):
,
,
Sets the rate of acceleration for all speed increases.
Values
Default:
20.00 Secs
Min/Max:
0.00/600.00 Secs
Display:
0.01 Secs
Maximum Freq
Accel Time
Accel Rate
=
Speed
0
Time
P035 [Maximum Freq]
P039 or A147
[Accel Time x]
P040 or A148
[Decel Time x]
0
Acceleratio
n
Deceleration
Summary of Contents for PowerFlex400
Page 42: ...1 32 Installation Wiring Notes...
Page 52: ...2 10 Start Up Notes...
Page 112: ...3 60 Programming and Parameters Notes...
Page 128: ...A 8 Supplemental Drive Information Notes...
Page 164: ...D 14 Application Notes Notes...
Page 170: ...E 6 Modbus RTU Protocol Notes...
Page 178: ...F 8 Metasys N2 Notes...
Page 190: ...Index 4...
Page 191: ......