Troubleshooting
No.
Fault
Ty
p
e
(1
)
Description
Action
F33
Auto Rstrt Tries
➁
Drive unsuccessfully attempted
to reset a fault and resume
running for the programmed
number of
[Auto Rstrt
Tries].
Correct the cause of the fault and
manually clear.
F38
Phase U to Gnd
➁
A phase to ground fault has been
detected between the drive and
motor in this phase.
1. Check the wiring between the
drive and motor.
2. Check motor for grounded
phase.
3. Replace drive if fault cannot be
cleared.
F39
Phase V to Gnd
F40
Phase W to Gnd
F41
Phase UV Short
➁
Excessive current has been
detected between these two
output terminals.
1. Check the motor and drive output
terminal wiring for a shorted
condition.
2. Replace drive if fault cannot be
cleared.
F42
Phase UW Short
F43
Phase VW Short
F48
Params
Defaulted
The drive was commanded to
write default values to EEPROM.
1. Clear the fault or cycle power to
the drive.
2. Program the drive parameters as
needed.
F63
SW OverCurrent
➀
Programmed
[SW Current
Trip] has been exceeded.
Check load requirements and
[SW Current Trip] setting.
F64
Drive Overload
➁
Drive rating of 110% for 1 minute
or 150% for 3 seconds has been
exceeded.
Reduce load or extend Accel Time.
F70
Power Unit
➁
Failure has been detected in the
drive power section.
1. Cycle power.
2. Replace drive if fault cannot be
cleared.
F71
Net Loss
The communication network has
faulted.
1. Cycle power.
2. Check communications cabling.
3. Check network adapter setting.
4. Check external network status.
F81
Comm Loss
➁
RS485 (DSI) port stopped
communicating.
1. Check RS485 wiring connection.
2. Check if a communications
adapter or HIM was
disconnected.
3. Increase
[Comm Loss
Time] to an appropriate time for
application.
4. Change
[Comm Loss
Action] to a value other than “0”
(fault), if appropriate for the
application.
F94
Function Loss
➁
[Start Source] is set to
setting 6. The input to terminal 01
has been opened.
Close input to terminal 01 and
re-start the drive.
F100 Parameter
Checksum
➁
The checksum read from the
board does not match the
checksum calculated.
[Reset To Defalts] to option
1 “Reset Defaults”.
Summary of Contents for PowerFlex400
Page 42: ...1 32 Installation Wiring Notes...
Page 52: ...2 10 Start Up Notes...
Page 112: ...3 60 Programming and Parameters Notes...
Page 128: ...A 8 Supplemental Drive Information Notes...
Page 164: ...D 14 Application Notes Notes...
Page 170: ...E 6 Modbus RTU Protocol Notes...
Page 178: ...F 8 Metasys N2 Notes...
Page 190: ...Index 4...
Page 191: ......