
Metasys N2
F-7
Writing Parameter Values
These outputs are written each time the User OUTx point is written from
the network.
The Param# for OUTx’s default to commonly accessed parameters and
can be changed if desired. A value of “0” in the Param# for OUTx field
disables the writing of data for that specific point.
Figure F.2 Configurable Objects: Outputs
!
ATTENTION:
Risk of equipment damage exists. If configurable
outputs are programmed to write parameter data to Non-Volatile
Storage (NVS) frequently, the NVS will quickly exceed its life cycle
and cause the drive to malfunction. Do not create a program that
frequently uses configurable outputs to write parameter data to NVS.
Table F.14 Configurable Objects: Outputs
Network Point
Description
Range
Default
Type
(NPT)
Address
(NPA)
AO
6
User OUT1
Varies by the parameter
selected by Param# for
OUTx.
0
AO
7
User OUT2
0
AO
8
User OUT3
0
AO
9
User OUT4
0
ADI
5
User OUT1 (A06)
Destination (Param#)
0 (not in use), 1 to
maximum # of drive
parameters
A154 [PID Prop Gain]
ADI
6
User OUT2 (A07)
Destination (Param#)
0 (not in use), 1 to
maximum # of drive
parameters
A155 [PID Integ Time]
ADI
7
User OUT3 (A08)
Destination (Param#)
0 (not in use), 1 to
maximum # of drive
parameters
A156 [PID Diff Rate]
ADI
8
User OUT4 (A09)
Destination (Param#)
0 (not in use), 1 to
maximum # of drive
parameters
A158 [PID Deadband]
Controller
Drive
Param#
for OUTx
User
OUTx
ADI
AO
Summary of Contents for PowerFlex400
Page 42: ...1 32 Installation Wiring Notes...
Page 52: ...2 10 Start Up Notes...
Page 112: ...3 60 Programming and Parameters Notes...
Page 128: ...A 8 Supplemental Drive Information Notes...
Page 164: ...D 14 Application Notes Notes...
Page 170: ...E 6 Modbus RTU Protocol Notes...
Page 178: ...F 8 Metasys N2 Notes...
Page 190: ...Index 4...
Page 191: ......