D-6
Application Notes
Analog PID Reference Signals
Parameters
[Analog In 1 Hi],
[Analog In 2 Lo], and
[Analog In 2 Hi] are used to scale or invert
an analog PID Reference.
Examples
Scale Function
For a 0-5 volt signal, the following parameter settings are used so that a 0
volt signal = 0% PID Reference and a 5 volt signal = 100% PID
Reference.
•
[Analog In 1 Sel] or
[Analog In 2 Sel] = 2 “Voltage Mode
- Unipolar”.
•
[Analog In 1 Lo] or
[Analog In 2 Lo] = 0.0%
•
[Analog In 1 Hi] or
[Analog In 2 Hi] = 50.0%
•
[PID Ref Sel] = 0 “0-10V Input”
Invert Function
For a 4-20mA signal, the following parameter settings are used so that a
20mA signal = 0% PID Reference and a 4mA signal = 100% PID
Reference.
•
[Analog In 1 Sel] or
[Analog In 2 Sel] = 1 “Current
Mode 4-20 mA”
•
[Analog In 1 Lo] or
[Analog In 2 Lo] = 100.0%
•
[Analog In 1 Hi] or
[Analog In 2 Hi] = 0.0%
•
[PID Ref Sel] = 2 “Analog In 1” or 3 “Analog In 2”
0 10 20 30 40 50 60 70 80 90 100
PID Reference (%)
Input V
olts
2
4
6
8
10
12
0 10 20 30 40 50 60 70 80 90 100
PID Reference (%)
4-20mA Input
4
8
12
16
20
24