P1 – Floor Level Network (FLN)
G-3
a.
Points not listed are not used in this application.
b.
A single value in a column means that the value is the same in English units and in SI units.
c.
Point numbers that appear in brackets { } may be unbundled at the field panel.
*1
Depends on drive model
*2
1 / Secs
*3
Depending on configuration, units can be volts or milliamperes.
*4
Local Control causes the drive to use
[Start Source 2] and
[Speed Ref 2] for start and
speed reference control.
65
LAO
PID GAIN
1
PTC
0.01
0
–
–
66
LAO
PID INT TIME
2
SEC
0.1
0
–
–
67
LAO
PID DIF RATE
0
PERSEC
*2
0.01
0
–
–
68
LAO
PID SETPOINT
0
PTC
0.1
0
–
–
{70}
LDI
CMD DIR MON
FWD
–
1
0
REV
FWD
{71}
LDI
ACCELERATING
OFF
–
1
0
ON
OFF
{72}
LDI
DECELERATING
OFF
–
1
0
ON
OFF
{73}
LDI
ALARM
NORMAL
–
1
0
ALARM
NORMAL
{74}
LDI
AT SPEED
OFF
–
1
0
ON
OFF
{75}
LDI
MAIN FREQ
OFF
–
1
0
ON
OFF
{76}
LDI
OPER CMD
OFF
–
1
0
ON
OFF
{77}
LDI
PARAM LOCK
UNLOCK
–
1
0
LOCK
UNLOCK
{78}
LDO
JOG
OFF
–
1
0
ON
OFF
{79}
LDO
LOCAL CNTRL
*4
OFF
–
1
0
ON
OFF
{80}
LDO
MOP INC
OFF
–
1
0
ON
OFF
{81}
LDO
ACCEL RATE 1
OFF
–
1
0
ON
OFF
{82}
LDO
ACCEL RATE 2
OFF
–
1
0
ON
OFF
{83}
LDO
DECEL RATE 1
OFF
–
1
0
ON
OFF
{84}
LDO
DECEL RATE 2
OFF
–
1
0
ON
OFF
{85}
LDO
REF SELECT 1
OFF
–
1
0
ON
OFF
{86}
LDO
REF SELECT 2
OFF
–
1
0
ON
OFF
{87}
LDO
REF SELECT 3
OFF
–
1
0
ON
OFF
{88}
LDO
MOP DEC
OFF
–
1
0
ON
OFF
{92}
LAO
REFERENCE
0
PCT
0.01
0
–
–
{93}
LDI
OK.FAULT
OK
–
1
0
FAULT
OK
{94}
LDO
RESET FAULT
NORMAL
–
1
0
RESET
NORMAL
{99}
LAO
ERROR STATUS
0
–
1
0
–
–
Table G.1 Point Database for Application 2735
Point
Number
Point
Type
Subpoint Name
Factory
Default
(SI Units)
Engineering
Units
(SI Units)
Slope
(SI Units)
Intercept
(SI Units)
On Text
Off Text
Summary of Contents for PowerFlex400
Page 42: ...1 32 Installation Wiring Notes...
Page 52: ...2 10 Start Up Notes...
Page 112: ...3 60 Programming and Parameters Notes...
Page 128: ...A 8 Supplemental Drive Information Notes...
Page 164: ...D 14 Application Notes Notes...
Page 170: ...E 6 Modbus RTU Protocol Notes...
Page 178: ...F 8 Metasys N2 Notes...
Page 190: ...Index 4...
Page 191: ......