Supplemental Drive Information
A-3
Category
Specification
Agency
Certification
Listed to UL508C and CAN/CSA-22.2
Listed to UL508C for plenums
Certified to AS/NZS, 1997 Group 1, Class A
Marked for all applicable European Directives
EMC Directive (89/336)
EN 61800-3, EN 50081-1, EN 50082-2
Low Voltage Directive (73/23/EEC)
EN 50178, EN 60204
The drive is also designed to meet the appropriate portions of the following specifications:
NFPA 70 - US National Electrical Code
NEMA ICS 3.1 - Safety standards for Construction and Guide for Selection, Installation and
Operation of Adjustable Speed Drive Systems.
IEC 146 - International Electrical Code.
Protection
Bus Overvoltage Trip:
200-240V AC Input: 405V DC bus voltage (equivalent
to 290V AC incoming line)
380-460V AC Input: 810V DC bus voltage (equivalent
to 575V AC incoming line)
Bus Undervoltage Trip:
200-240V AC Input: 210V DC bus voltage (equivalent
to 150V AC incoming line)
380-480V AC Input: 390V DC bus voltage (equivalent
to 275V AC incoming line)
Power Ride-Thru:
100 milliseconds
Logic Control Ride-Thru:
0.5 seconds minimum, 2 seconds typical
Electronic Motor Overload Protection:
I
2
t protection - 110% for 60 seconds (Provides Class
10 protection)
Overcurrent:
180% hardware limit, 220% instantaneous fault
Ground Fault Trip:
Phase-to-ground on drive output
Short Circuit Trip:
Phase-to-phase on drive output
Environment
Altitude:
1000 m (3300 ft) max. without derating. Above 1000 m
(3300 ft) derate 3% for every 305 m (1000 ft).
Maximum Surrounding Air Temperature
without derating:
IP20, Open Type:
IP30, NEMA Type 1, UL Type 1:
–10 to 50 degrees C (14 to 122 degrees F)
–10 to 45 degrees C (14 to 113 degrees F)
Cooling Method:
Fan: All drive ratings
Storage Temperature:
–40 to 70 degrees C (–40 to 158 degrees F)
Atmosphere:
Important:
Drive
must
not
be installed in an area
where the ambient atmosphere contains volatile or
corrosive gas, vapors or dust. If the drive is not going to
be installed for a period of time, it must be stored in an
area where it will not be exposed to a corrosive
atmosphere.
Relative Humidity:
0 to 95% non-condensing
Shock (operating):
15G peak for 11ms duration (
±
1.0 ms)
Vibration (operating):
1G peak, 5 to 2000 Hz
Seismic Rating
Meets the seismic requirements of the 2003
International Building Code as specified by AC156.
UL
®
C
US
Summary of Contents for PowerFlex400
Page 42: ...1 32 Installation Wiring Notes...
Page 52: ...2 10 Start Up Notes...
Page 112: ...3 60 Programming and Parameters Notes...
Page 128: ...A 8 Supplemental Drive Information Notes...
Page 164: ...D 14 Application Notes Notes...
Page 170: ...E 6 Modbus RTU Protocol Notes...
Page 178: ...F 8 Metasys N2 Notes...
Page 190: ...Index 4...
Page 191: ......