7-8
Troubleshooting
25
Bad I/O
Fragment
A DeviceNet I/O fragment was received out of sequence.
Possible line noise problem.
26
Idle I/O
Message
The DeviceNet scanner was placed in program mode.
27
Peer I/O
Timeout
The adapter has not received Peer I/O from another device on
the network within the specified time-out interval.
28
DPI Fault
Clear
The DPI product issued this because a fault was cleared.
29
DN COS
Timeout
A Change of State (COS) connection has timed out.
30
DN Poll
Allocate
A Polled connection has been allocated.
31
DN COS
Allocate
A Change of State (COS) I/O connection has been allocated.
32
DN Poll
Closed
A Polled I/O connection was explicitly closed.
33
DN COS
Closed
A Change of State (COS) connection was explicitly closed.
34
Flt Cfg Error
At least one of the Fault Configuration parameters contains a
value greater than 65535 and the DPI product expects a 16-bit
value.
35
DN Dup MAC
Fault
Module has detected another node on DeviceNet using the
same node address that it is using.
36
Manual Reset The module was reset by the user.
37
Language
CRC Bad
The language text memory segment is corrupt.
Code
Event
Description