3-10
Configuring the Adapter
To set an adapter to transmit Peer-to-Peer data
1.
Verify that
Parameter 41 - [Peer Out Enable]
is set to
Off
. This
parameter must be set to Off while you configure some of the peer
output parameters.
Figure 3.10 Peer Out Enable Screen on an LCD HIM
2.
Select the source of the data to output to the network in
Parameter
39 - [Peer A Output]
.
Figure 3.11 Peer A Output Screen on an LCD HIM
If you are transmitting a 32-bit Reference or 32-bit Datalink, only
Peer A Output will be available. Peer B Output cannot be used.
3.
If desired, select an additional source of the data to output to the
network in
Parameter 40 - [Peer B Output]
.
Figure 3.12 Peer B Output Screen on an LCD HIM
Value Setting
0
Off (Default)
1
On
Port 5 Device
20-COMM-D
Parameter #: 41
Peer Out Enable
0
Off
Port 5 Device
20-COMM-D
Parameter #: 39
Peer A Output
1
Cmd/Ref
Value
Description
0
Off (Default)
1
Logic Command/Reference
2 - 5
Datalink A, B, C, or D
Input
6 - 9
Datalink A, B, C, or D
Output
Port 5 Device
20-COMM-D
Parameter #: 40
Peer B Output
2
DL A Input
Value
Description
0
Off (Default)
1
Logic Command/Reference
2 - 5
Datalink A, B, C, or D
Input
6 - 9
Datalink A, B, C, or D
Output
Summary of Contents for PowerFlex 20-COMM-D
Page 1: ...DeviceNet Adapter 20 COMM D FRN 1 xxx User Manual...
Page 6: ...iv Table of Contents Notes...
Page 72: ...6 14 Using Explicit Messaging Notes...
Page 90: ...B 8 Adapter Parameters Notes...
Page 122: ...C 32 DeviceNet Objects Notes...
Page 132: ...E 8 Master Slave I O Configuration Notes...
Page 148: ......