Very High Speed Counter Module Input and Output Data
Pulse Width Modulation (PWM) Value (Output Word 3)
When the module is programmed for a
PWM [3]
configuration, the
time base is enabled, the counter, rollover the 1
st
ON and 1
st
OFF
value for the respective channel are used. Ties can be used to direct
the PWM signal to any or both outputs. The range of PWM values is 0
≤
value
≤
9500 decimal (i.e. 0.00%
≤
value
≤
95.00%). Entering a value
“below” 0 will result in a PWM of 0%; a value greater than 9500 will
result in a PWM of 95.00%. The actual duty cycle observed at the
output will depend on the turn on and turn off times of the MOSFET,
the energy storage capability of the cable/load and the resistance from
output to return.
Configuration Data
The following represents the configuration data used by the
1734-VHSC24 module.
Counter Configuration (Configuration Word 1)
Use this byte to select the type of counter desired.
07
06
05
04
03
02
01
00
ZI
MD
CF
Counter 0
0
0
0
0
Counter
0
0
0
1
Encoder X1
0
0
1
0
Encoder X2
0
0
1
1
PWM
0
1
0
0
Encoder X4
0
1
0
1
Period/Rate
0
1
1
0
Continuous/Rate
0
1
1
1
Rate Measurement
0
0
0
Store Count Disabled
0
0
1
Mode 1 - store/continue
0
1
0
Mode 2 - store/wait/resume
0
1
1
Mode 3 - store, reset/wait/start
1
0
0
Mode 4 - store, reset/start
1
0
1
Reserved
1
1
0
Reserved
1
1
1
Reserved
0
Z input - 0 = not inverted
1
Z input - 1 = inverted