1
Publication 1734-UM003A-EN-P - August 2000
Chapter
2
Installing the Very High Speed Counter
Module
General
The 1734-VHSC is a two-module set. Module 1 houses the 1734-VHSC
functionality while module 2 provides screw terminals necessary to
access chassis ground (Chas Gnd) and common (C). Module 2 also
connects terminal 4 to 5 and terminal 6 to 7 for ease of wiring power
to the input device. Module 2 is not necessary for VHSC functionality
but eases customer wiring. Module 2 does not use a node address,
and it doesn’t consume power from the PointBus. To reduce loop
area, place module 2 adjacent (either side) to module 1
Installing the Mounting Base/
Wiring Base Assembly
The wiring base assembly (1734-TB or -TBS) consists of a mounting
base (cat. no. 1734-MB) and a removable terminal block (cat. no.
1734-RTB or -RTBS). You can install the assembly, or just the
mounting base. To install the mounting base/wiring base assembly on
the DIN rail, proceed as follows.
1.
Position the mounting base/wiring base assembly vertically
above the installed units (adapter, power supply or existing
module).
2.
Slide the mounting base down allowing the interlocking side
pieces to engage the adjacent module or adapter.