Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
231
Specifications
Appendix
A
For the Micro870 controller relay chart, see
Micro850, and Micro870 Controllers on page 234
.
Output Specifications
Attribute
2080-LC70-24AWB,
2080-LC70-24QWB,
2080-LC70-24QWBK
2080-LC70-24QBB, 2080-LC70-24QBBK
Relay Output
Hi-Speed Output
(Outputs 0...1)
Standard Output
(Outputs 2 and higher)
Number of outputs
10
2
8
Output voltage, min
5V DC, 5V AC
10.8V DC
10V DC
Output voltage, max
125V DC, 265V AC
26.4V DC
26.4V DC
Load current, min
10 mA
Load current,
continuous, max
2.0 A
100 mA (high-speed operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
1.0 A @ 30 °C
0.3 A @ 65 °C (standard operation)
Surge current, per point
See Relay Contacts Ratings on page
216
4.0 A for 10 ms every 1 s @ 30 °C; every 2 s @ 65 °C
(1)
Current, per common, max
5 A
–
–
Turn on time/
Turn off time, max
10 ms
2.5
µ
s
ON: 0.1 ms
OFF: 1 ms
(1) Applies for general purpose operation only; does not apply for high-speed operation.
Relay Contacts Ratings
Maximum Volts
Amperes
Amperes
Continuous
Volt-Amperes
Make
Break
Make
Break
120V AC
15 A
1.5 A
2.0 A
1800V A
180V A
240V AC
7.5 A
0.75 A
24V DC
1.0 A
1.0 A
28V A
125V DC
0.22 A
0.22 A
Summary of Contents for Micro830
Page 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Page 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Page 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Page 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Page 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...