224
Rockwell Automation Publication 2080-UM002K-EN-E - March 2019
Appendix A
Specifications
Micro850 48-Point Controllers
General Specifications
Attribute
2080-LC50-48AWB
2080-LC50-48QWB
2080-LC50-48QVB
2080-LC50-48QBB
Number of I/O
48 (28 inputs, 20 outputs)
Dimensions (HxWxD)
90 x 238 x 80 mm (3.54 x 9.37 x 3.15 in.)
Shipping weight, approx.
0.725 kg (1.60 lb)
Wire size
0.2…2.5 mm
2
(24…14 AWG) solid copper wire or
0.2…2.5 mm
2
(24…14 AWG) stranded copper wire
rated @ 90 °C (194 °F) insulation max
Wiring category
(1)
2 – on signal ports
2 – on power ports
2 – on communication ports
Wire type
Use Copper Conductors only
Terminal screw torque
0.4…0.5 Nm (3.5…4.4 lb-in.)
(using a 0.6 x 3.5 mm flat-blade screwdriver)
Input circuit type
120V AC
12/24V sink/source (standard)
24V sink/source (high-speed)
Output circuit type
Relay
24V DC sink
(standard and high-speed)
24V DC source
(standard and high-speed)
Power consumption, max
11 W – without plug-in modules and expansion I/O modules
33 W –with plug-in modules and expansion I/O modules
Power supply voltage range
20.4…26.4V DC Class 2
I/O rating
Input:
120V AC, 16 mA
Output:
2 A, 240V AC,
2 A, 24V DC
Input:
24V, 8.8 mA
Output:
2 A, 240V AC,
2 A, 24V DC
Input:
24V, 8.8 mA
Output:
24V DC, 1 A per point
(surrounding air temperature 30 °C)
24V DC, 0.3 A per point
surrounding air temperature 65 °C)
Insulation stripping length
7 mm (0.28 in)
Enclosure type rating
Meets IP20
Pilot duty rating
C300, R150
–
Isolation voltage
250V (continuous),
Reinforced Insulation Type,
Output to Aux and Network,
Inputs to Outputs.
Type tested for 60 s @
3250V DC Output to Aux and
Network, Inputs to Outputs.
150V (continuous),
Reinforced Insulation Type
Input to Aux and Network
Type tested for 60 s @
1950V DC Input to Aux and
Network.
250V (continuous),
Reinforced Insulation Type,
Output to Aux and Network,
Inputs to Outputs
Type tested for 60 s @
3250V DC Output to Aux and
Network, Inputs to Outputs
50V (continuous),
Reinforced Insulation Type,
Input to Aux and Network
Type tested for 60 s @ 720V
DC, Inputs to Aux and
Network
50V (continuous), Reinforced Insulation Type, I/O to Aux
and Network, Inputs to Outputs
Type tested for 60 s @ 720V DC, I/O to Aux and Network,
Inputs to Outputs.
North American temp code
T4
(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication
Summary of Contents for Micro830
Page 6: ...vi Rockwell Automation Publication 2080 UM002K EN E March 2019 Preface Notes ...
Page 273: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 259 Quickstarts Appendix C ...
Page 300: ...286 Rockwell Automation Publication 2080 UM002K EN E March 2019 Appendix C Quickstarts Notes ...
Page 352: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 338 Index Notes ...
Page 353: ...Rockwell Automation Publication 2080 UM002K EN E March 2019 339 ...